AS-i 3.0 EtherNet/IP Gateway with integrated Safety Monitor
Operation in advanced display mode
This list contains entries for all AS-i slaves that were responsible for at least one
intermittent configuration error since the list was last read or since the AS-i mas-
ter was turned on.
9.6.8
ERROR COUNTERS
Main Menu|| DIAGNOSIS ||
ERROR COUNTERS
||
This list displays the fault counter for each single AS-i slave.
In addition, the number of voltage dropouts/undervoltage on AS-i (APF) is dis-
played.
Selecting RESET resets the fault counter to 0.
Selecting OK on a slave address displays a list with additional information:
empty field: no error
X: AS-i Slave triggered a configuration error.
ERROR COUNTERS
RESET
1A - 0
...
31A - 65535
1B - 34
...
30B - 0
SLAVE ADDR. 4A
NO SLV.:
5
NO SLV. TEL.:
31
SLV. TEL. ERR.:
1
PERIPH. FAULTS:
2
PROTOCOL FAULT:
1
Information
error discription
NO SLV
frequency of slave failure
NO SLV. TEL
number of missing slave telegrams
SLV. TEL. ERR
number of slave telegram errors
PERIPH. FAULTS
number of peripheral faults
PROTOCOL FAULT
number of superior protocol faults (i.e. CTT2)