Power Supply PS1000-D2-24.40.RM
Application Notes
20
21
-1
1
27
19.6
Mounting Orientations
Mounting orientations other than input terminals on the bottom and output terminals on the top
require a reduction in continuous output power or a limitation in the maximum allowed ambient
temperature.
The amount of reduction influences the lifetime expectancy of the power supply.
Therefore, two different derating curves for continuous operation can be found below:
Curve A1
Recommended output current.
Curve A2
Max allowed output current (results in approximately half the lifetime
expectancy of A1).
Figure 19.4 Mounting orientation A (standard orientation)
Figure 19.5 Mounting orientation B (upside down)
Figure 19.6 Mounting orientation C (table-top mounting)
Figure 19.7 Mounting orientation D (horizontal cw)
Redundancy
Module
OUTPUT
INPUTS
Output Current
0
10
20
30
40
60°C
10
20
30
40A
50
A1
Ambient Temperature
R edunda
nc y
Module
O U
T PU
T
IN PU
T S
Output Current
0
10
20
30
40
60°C
10
20
30
40A
50
A1
Ambient Temperature
Output Current
0
10
20
30
40
60°C
10
30
40A
50
20
A1
A2
Ambient Temperature
R
e
dunda
nc
y
Modul
e
OU
T
P
U
T
IN
P
U
T
S
Output Current
0
10
20
30
40
60°C
10
30
40A
50
20
A1
A2
Ambient Temperature