Power Supply PS1000-D2-24.40.RM
Terminals and Wiring
8
Terminals and Wiring
To connect the chassis to ground, use a ring-type terminal (ring cable lug) which is suitable
for a M4 screw and connect it to the chassis ground terminal on top of the unit.
Connecting Terminals
1.
The external circuitry of all terminals must meet the safety requirements stipulated by
IEC/EN/UL 60950-1: SELV.
2.
Use appropriate copper cables that are designed for minimum operating temperatures of:
•
60°C for ambient up to 45°C and
•
75°C for ambient up to 60°C minimum
•
90°C for ambient up to 70°C minimum.
3.
Follow national installation codes and installation regulations!
4.
Ensure that all strands of a stranded wire enter the terminal connection!
5.
Screws of unused terminal compartments should be securely tightened.
6.
Ferrules are allowed.
7.
Do not connect or disconnect the wires from the terminals below -25°C (-13°F).
Input
Output
Type
Screw termination
IP20 Finger safe construction.
Suitable for field installation.
Screw termination
IP20 Finger safe construction.
Suitable for field installation.
Solid wire
0.5-6mm
2
0.5-16mm
2
Stranded wire
0.5-4mm
2
0.5-10mm
2
American Wire Gauge
20-10 AWG
22-8 AWG
Max. wire diameter
2.8mm (including ferrule)
5.2mm (including ferrules)
Wire stripping length
7mm / 0.275inch
12mm / 0.5inch
Screwdriver
3.5mm slotted or Pozidrive No 2 3.5mm slotted or Pozidrive No 2
Recommended tightening torque
0.8Nm, 7lb.in
1.2Nm, 10.6lb.in