Power Supply PS1000-A6-24.20.R
Terminals and Wiring
15
Terminals and Wiring
The terminals are IP20 finger safe constructed and suitable for field- and factory wiring.
Connecting Terminals
1.
Use appropriate copper cables that are designed for minimum operating temperatures of:
•
60°C for ambient up to 45°C and
•
75°C for ambient up to 60°C minimum
•
90°C for ambient up to 70°C minimum.
2.
Follow national installation codes and installation regulations!
3.
Ensure that all strands of a stranded wire enter the terminal connection!
4.
Unused terminal compartments should be securely tightened.
5.
Ferrules are allowed and recommended.
Input
Output
DC-OK-Signal
Type
Plug connector with
screw termination
Plug connector with
screw termination
Plug connector with
screw termination
Solid wire
Max. 4mm
2
Max. 6mm
2
Max. 1.5mm
2
Stranded wire
Max. 2.5mm
2
Max. 6mm
2
Max. 1.5mm
2
American Wire Gauge
AWG 20-12
AWG 24-10
AWG 26-14
Max. wire diameter (including
ferrules)
2.4mm
3.2mm
1.8mm
Recommended tightening torque
Max. 0.5Nm, 4.5lb-in Max. 0.6Nm, 5.3lb-in Max. 0.8Nm, 7lb-in
Wire stripping length
7mm / 0.28inch
12mm / 0.47inch
6mm / 0.24inch
Screwdriver
3.5mm slotted or
cross-head No 2
3.5mm slotted or
cross-head No 2
3mm slotted
Do not unplug the
connectors more often
than 20 times in total
Do not unplug the
connectors more often
than 20 times in total
Do not unplug the
connectors more often
than 20 times in total