Power Supply PS1000-A6-24.20.R
DC-OK Relay Contact
10
DC-OK Relay Contact
This feature monitors the output voltage of the power supply in front of the decoupling device
(see also chapter 14.)
Figure 10.1 DC-OK relay contact behavior
Contact closes
As soon as the output voltage reaches typ. 22Vdc.
Contact opens
As soon as the output voltage dips below 22Vdc.
Short dips will be extended to a signal length of 100ms. Dips shorter than 1ms will
be ignored.
Switching hysteresis 1V
Contact ratings
Maximal 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A, resistive load
Minimal permissible load: 1mA at 5Vdc
Isolation voltage
See dielectric strength table in chapter 21.
100ms
22Vdc
<
1ms
open
open
closed
closed
>
1...4ms