Output function in normal operation

Voltage output:

If the measurement range is exceeded, the analog output value retains the last displayed 

value until the position of the actuator falls within the analog measurement range again 

(shown in the example).

9. Output signals

7.1

Function of switching outputs S1 and S2

The position of the actuator defined by the angular positioning system is based on half of the 

actuator width (center of the actuator). The signaling zones are preset to the angle settings 

120

°

... 125 

°

 (S1) and 240

°

 ... 245

°

 (S2) at the factory. The switch-on and switch-off points of 

the signaling zone can be programmed at any desired position. However, the minimum 

signaling zone width is 5 

°

If the actuator falls between S11 and S12 or S21 and S22 in the programmed signaling zone, 

the corresponding switching output is activated. When a switching output is active, the 

corresponding yellow LED lights up. If the actuator is positioned outside of a programmed 

signaling zone, the relevant switching output changes to an idle state. When the actuator 

leaves the detection area of the angular positioning system (loss of actuator), an active 

switching output changes to an idle state ("up" position) and a switching output already in an 

idle state remains in this state. The "Power/Error" LED lights up red when the actuator is lost.

7.2

Function of the analog output I/U

Function in normal operation

The position of the actuator defined by the angular positioning system is based on half of the 

actuator width (center of the actuator). The start point of the analog output is preset to the 

angular position 0

°

 and the analog measuring range is set to a full 360

°

 in the factory. The start 

and end points of the analog measuring range can be defined by programming each relevant 

angular position, the only restriction being that the analog measurement range must fall 

between 45

°

 and 360

°

 . 

After switching on, the angular positioning system automatically evaluates the load connected 

at the analog output. If the load is a low resistance load (<400 

), the analog output assumes 

the function of a current output 4 ... 20 mA. If the load is a high resistance load (>3.3 k

), the 

analog output assumes the function of a voltage output 0 ... 10 V. A change in the load 

properties during operation is not evaluated.

The analog output shows the minimum value of the relevant value range (4 mA or 0 V) at the 

start position (I/U1). If the actuator rotates towards the programmed end position (I/U2), the 

output value increases proportionally in relation to the rotation angle covered. When the 

programmed end position is reached (I/U2), the analog output shows its maximum value (20 

mA or 10 V). If the actuator moves within the area of the programmed measurement range, the 

corresponding yellow LED lights up. If the actuator rotates beyond the limits of the programmed 

measurement range, the LED goes out. The function of the output depends on whether the 

analog output assumes the function of a voltage or a current output.

Current output:

If the measurement range is exceeded, the analog output value adopts the error signal 3.6 mA. 

The current output delivers this fault current until the position of the actuator falls within the 

programmed analog measurement range again.

Caution!

Make sure that the connected load is always low resistance (

400 

) or high resistance (

3.3 

k

).

If a load is connected with an impedance between 400 

 and 3.3 k

, this may result in 

undefined output values because the sensor cannot fully control the analog output. The 

function of the output (current or voltage output) is not defined either.

Содержание PMI360DV-F130-IU2E2-V15

Страница 1: ...PMI360DV F130 IU2E2 V15 Inductive angle positioning system FACTORY AUTOMATION MANUAL...

Страница 2: ...of Delivery for Products and Services of the Electrical Indus try published by the Central Association of the Electrical Industry Zentralverband Elektrotechnik und Elektroindustrie ZVEI e V in its mos...

Страница 3: ...cessories 10 4 4 1 Connecting cable 10 4 4 2 Actuator 10 5 Installation 11 5 1 Note on safety 11 5 2 Mounting 11 5 3 Electrical connection 13 6 Commissioning 14 6 1 Programming the switching outputs 1...

Страница 4: ...4 PMI360DV F130 IU2E2 V15 9 Troubleshooting 21 9 1 Faults when programming the outputs 21 9 2 Faults during operation 22 10 Disposal 23...

Страница 5: ...gy on a worldwide scale Symbols used The following symbols are used in this manual Handling instructions You will find handling instructions beside this symbol Contact If you have any questions about...

Страница 6: ...developed and manufactured under observance of the applicable European standards and guidelines The product manufacturer Pepperl Fuchs GmbH D 68307 Mannheim has a certified quality assurance system t...

Страница 7: ...e performed by a trained professional only User modification and or repair are dangerous and will void the warranty and exclude the manufacturer from any liability If serious faults occur stop using t...

Страница 8: ...s an analog output for the indication of angular positions For high resistance loads 3 3 k the angular position will output a voltage value 0 10 V DC and for low resistance loads 400 a current value 4...

Страница 9: ...e the start and end points of the analog output and the outer S1 and S2 buttons are used to configure the start and end of the detection zone of the two switching outputs on the sensor The S1 S2 and I...

Страница 10: ...at may be used in electrically noisy installation environments 4 4 2 Actuator The BT F130 A actuator is designed for mounting directly on the drive shaft or a servodrive Figure Material Length Order d...

Страница 11: ...ctuator The actuator must not make physical contact or scratch the sensors surface when moving Using a different actuating element You may use a different actuator instead of the BT F130 A actuator pr...

Страница 12: ...inner surface E Sensor F Insert the shaft until actuator C and the sensitive surface on sensor D overlap as far as possible Dimension Value t 2 mm w 7 5 mm d1 Depending on the drive shaft material S23...

Страница 13: ...4 Check that the wires are connected correctly before connecting the cordset to the sensor On Pepperl Fuchs cordsets the wire colors are assigned to the connecting pins in the connector according to...

Страница 14: ...he device is ready for you to teach in the signaling zone end point 5 Move the actuator to the position that you wish to define as the signaling zone end point The rotation direction of the actuator i...

Страница 15: ...The yellow I U LED lights up for 2 seconds and then starts to flash again This indicates that the device is ready for you to teach in the end point of the analog ramp 4 Move the actuator to the posit...

Страница 16: ...If you intend to program an angle segment of exactly 360 for the analog output you can make use of the restriction that prevents the angle segment from exceeding 360 In the second step of the angle se...

Страница 17: ...tion of the second switching point of switching output S2 example 310 6 Start position of analog output S3 example 20 7 End position of analog output S3 example 110 8 Angular range outside of analog m...

Страница 18: ...ry The start and end points of the analog measuring range can be defined by programming each relevant angular position the only restriction being that the analog measurement range must fall between 45...

Страница 19: ...ctuator leaves the detection range of the angular positioning system e g actuator is removed the function of the output depends on whether the analog output assumes the function of a voltage or a curr...

Страница 20: ...he associated yellow LED starts to flash slowly after 2 seconds 2 Continue to hold the sensor button The LED begins to flash more quickly after an additional 10 seconds 3 Then release the button withi...

Страница 21: ...actuator mounted too far away from the surface of the sensor Mount actuator according to specifications see chapter 5 2 Power Error LED lights up red during programming Actuator lost during the param...

Страница 22: ...3 6 mA No actuator in the detection area of the sensor or unreliable detection of the actuator Check that the actuator used is mounted correctly or install an actuator with appropriate dimensions at...

Страница 23: ...osal Electronic waste is hazardous waste When disposing of the equipment observe the current statutory requirements in the respective country of use as well as local regulations The device does not co...

Страница 24: ...hs GmbH 68307 Mannheim Germany Tel 49 621 776 0 E mail info de pepperl fuchs com USA Headquarters Pepperl Fuchs Inc Twinsburg Ohio 44087 USA Tel 1 330 4253555 E mail sales us pepperl fuchs com Asia Pa...

Отзывы: