Warning Device NVO5-111
Commissioning
23
3953
20
12-
04
EN - 15
EN
Configuring the Functions
Switches
Description
DIP 4
SELECTION LEVEL
(alarm function type)
A
Position A: max. alarm
Oil layer thickness achieved (KVF sensor)
High liquid level (NVF sensor)
B
Position B: min. alarm
Low liquid level (NVF sensor)
DIP 5
SOUND AT ALARM
(audible alarm)
OFF
The audible alarm is not active.
ON
The audible alarm is active.
DIP 6
SIGNAL RELAY (signal
relay)
HLD.ALARM
The signal relay tracks the alarm relay and
performs a hold function at the same time. The
hold function can be reset.
INV.SIGNAL
The signal relay tracks the sensor. The signal
relay is activated in the event of an alarm.
DIP 7
REPEAT ALARM IN
24 HOURS (repeat
alarm)
OFF
The repeat alarm function is not active. After
pressing the "ALARM RESET" button, the audible
alarm is deactivated.
ON
The repeat alarm function is active. If the alarm
status is still active after 24 hours, after the alarm
was reset, the audible alarm is triggered again.
The volt-free relay contact switches.
DIP 8
RESET ALARM
FUNCTION
(ALARM RESET
activation)
ON
The "ALARM RESET" button is activated. The
audible alarm and the volt-free relay contact can
be reset.
OFF
The "ALARM RESET" button is deactivated. The
audible alarm and the volt-free relay contact
cannot be reset.