26 - EN
Universal Temperature Converter KCD2-UT2-(Ex)1
Editing device data
EN
7.4.4 Setting 0 mA ... 20 mA
At this setting, the start value of the measurement range is converted to 0 mA and the end value
to 20 mA. Intermediate values are converted proportionately.
Values less than the start value cannot be evaluated (output 0 mA). If the value exceeds the end
value, the output current increases linearly to a maximum of 20.5 mA (102.5 % of the measuring
range). Further increases cannot be evaluated (output 20.5 mA).
20.5
20.0
0
0
100
102.5
mA
% meas.
Start value
End value
range