Universal Temperature Converter KCD2-UT2-(Ex)1
Mounting and connection
81
39
68
20
13
-10
EN - 9
EN
If a current output is operated as a sink, the voltage across the terminals must be between 5 V and
30 V. An additional resistance is only required if the voltage is above 16.5 V. The resistance must
be between (U - 16.5 V)/0.0215 A and (U - 5 V)/0.0215 A (see diagram).
Example: U = 24 V
(24 V - 16.5 V)/0.0215 A = 350
(24 V - 5 V)/0.0215 A = 880
0
200
400
600
800
1000
1200
16
20
25
30
R [
Ω
]
U [V]
Resistance area