Universal Temperature Converter KCD2-UT2-(Ex)1
Configuration tools
EN
•
Undervoltage lockout
: the supply voltage is too low for the outputs to work properly, the outputs
return 0 mA or 0 V, no matter which fault current/which fault voltage has been selected
•
Sensor breakage
•
Sensor short circuit
: only RTD type of sensor; see section 7.2
•
Overrange
,
Underrange
: measured variable outside the maximum measuring range of the
selected sensor (see section 7.3 and section 7.4)
•
CJC Error
: if the cold junction compensation has been selected (see section 7.2) and a
breakage or short circuit occurs within the K-CJC-** terminal
•
Input
: terminals 1 to 4 (also uses terminal 4 for 4-wire resistance measurement)
6.6 Service
In menu Service the factory settings of the UT2 can be reloaded.
Reload the factory settings via pressing the button
Factory Reset
.