6
PENTALIFT EQUIPMENT CORPORATION
M086R06
December 8, 2017 10:37 AM
LDL Dock Lift Owners Manual
ELECTRICAL REFERENCE - 1 HP
Length of
branch circuit
which will have
a 2% voltage
drop at full load
current (copper
wire) ft/m.
The values
given are
intended to be
a rough wiring
guide only.
Be sure to
check all local
electrical codes
before wiring.
AWG
115/1/60
230/1/60
230/3/60
380/3/50
460/3/60
575/3/60
14
36 ft
143 ft
249 ft
865 ft
997 ft
1870 ft
12
57 ft
227 ft
396 ft
1376 ft
1586 ft
2973 ft
10
90 ft
362 ft
630 ft
2187 ft
2521 ft
4726 ft
8
143 ft
575 ft
1002 ft
3478 ft
4009 ft
7518 ft
6
228 ft
914 ft
1594 ft
5529 ft
6375 ft
11953 ft
Approximate Motor
Current (full load)
12 A
6 A
4.2 A
2 A
2.1 A
1.4 A
ELECTRICAL REFERENCE - 1.5 HP
Length of
branch circuit
which will have
a 2% voltage
drop at full load
current (copper
wire) ft/m.
The values
given are
intended to be
a rough wiring
guide only.
Be sure to
check all local
electrical codes
before wiring.
AWG
115/1/60
230/1/60
230/3/60
380/3/50
460/3/60
575/3/60
14
107 ft
209 ft
692 ft
838 ft
1455 ft
12
43 ft
171 ft
333 ft
1100 ft
1332 ft
2313 ft
10
68 ft
271 ft
529 ft
1749 ft
2118 ft
3676 ft
8
108 ft
432 ft
842 ft
2782 ft
3368 ft
5847 ft
6
172 ft
686 ft
1339 ft
4424 ft
5355 ft
9297 ft
Approximate Motor
Current (full load)
16 A
8 A
5 A
2.5 A
2.5 A
1.8 A