Installer Manual Siata V132-SFE-EV-VIRIDION - Installation
36 / 110
Ref. MKT-IM-009 / C - 08.06.2018
Length of connection pipes between valve and lower distribution system
The riser tube (distributor) must be cut between 12 to 17 mm, measured from the upper edge of the
tank. Remove the sharp edges (1 mm x 45°) to avoid damage to the seal during installation. See
drawing below.
Note
The riser tube (distributor) must be ISO PN 10 or higher standard:
minimum height 12 mm;
maximum height 17 mm;
chamfer 1 mm x 45°;
ISO PN10 or higher pipe.
Distributor tube
Содержание SIATA V132-SFE-EV-VIRIDION
Страница 1: ...SIATA V132 SFE EV VIRIDION INSTALLER MANUAL WATER PURIFICATION...
Страница 17: ...Installer Manual Siata V132 SFE EV VIRIDION Description Ref MKT IM 009 C 08 06 2018 17 110 3 3 Outline drawing...
Страница 77: ...Installer Manual Siata V132 SFE EV VIRIDION Maintenance Ref MKT IM 009 C 08 06 2018 77 110...
Страница 79: ...Installer Manual Siata V132 SFE EV VIRIDION Maintenance Ref MKT IM 009 C 08 06 2018 79 110...
Страница 81: ...Installer Manual Siata V132 SFE EV VIRIDION Maintenance Ref MKT IM 009 C 08 06 2018 81 110...
Страница 83: ...Installer Manual Siata V132 SFE EV VIRIDION Maintenance Ref MKT IM 009 C 08 06 2018 83 110...
Страница 85: ...Installer Manual Siata V132 SFE EV VIRIDION Maintenance Ref MKT IM 009 C 08 06 2018 85 110...
Страница 87: ...Installer Manual Siata V132 SFE EV VIRIDION Maintenance Ref MKT IM 009 C 08 06 2018 87 110...
Страница 89: ...Installer Manual Siata V132 SFE EV VIRIDION Maintenance Ref MKT IM 009 C 08 06 2018 89 110...
Страница 91: ...Installer Manual Siata V132 SFE EV VIRIDION Maintenance Ref MKT IM 009 C 08 06 2018 91 110...
Страница 110: ...www pentairaquaeurope com...