INSTALLATION

INSTALLATION

Pressure Tank Recommendations

Minimum tank size is 8 litres. Use a pre-
charged pressure tank with Drive, as shown in 
Table 6. The tank size must equal at least 20 
percent of the pump’s rated flow in litres per 
minute (LPM), but cannot be less than 8 litre 
capacity. For example, a pump rated at 30 LPM 
would require a tank of 8 litres capacity or 
larger. A pump rated at 200 LPM would require 
a 40 litre tank or larger. Tanks larger than 40 
litre can be used, but may require adjustment 
of Wake Delay parameter.

Table 7 - Control Pressure Set Point and Tank 
Pre-Charge Pressure Values (PSI).

Pressure 

Point 

Setting 

(kPa)

Precharge 

Pressure 

(kPa)

Pressure 

Point 

Setting 

(kPa)

Precharge 

Pressure 

(kPa)

170

120

440

310

205

145

480

340

240

170

510

360

270

190

545

380

310

220

580

410

350

245

610

430

375

265

650

455

414 

(Default)

290

NOTICE

 Set pressure tank’s pre-charge to 70 

percent of the system operating pressure. 
When using an external set point as well as 
an internal set point, pre-charge tank to 70 
percent of the lower setpoint of the two. 
Some applications may require a different 
percentage when determining the setpoint.

Transducer Connections

A 0-668 kPa 4-20 mA transducer is provided 
with Drive. Install the transducer downstream 
of tank, as shown in Figure 1. Install transducer 
in a tee in a straight section of pipe with at 
least 30cm of straight pipe on each side of the 
tee (i.e., all fittings must be at least 30cm away 
from transducer).
Feed transducer cable through the open 13mm 
conduit hole on bottom of the Drive enclosure.
As shown in Figure 9, connect the red wire 
of the transducer cable to AI+, connect black 
wire to AI–, and connect the green cable shield 
to the metal cable shield screw.

To connect the transducer wires:

1.  Strip wire 13mm
2.  Push spring terminal up with finger  

 

  or slotted screwdriver
3.  Insert wires from bottom
4.  Release spring terminal 
 

Input Power Connections

The input power terminals are located on 
the lower left side and are marked L1 and 
L2 (see Figure 9). There is a ground screw 
for the input ground wire to the right of the 
connector (torque to 1.5 Nm). Feed wire 
through the 20mm conduit hole on the bottom 
left side and into appropriate terminals. If wire 
is large enough to require a larger conduit 
hole, remove the 3.2cm knockout and use 
appropriate conduit connections.
To determine the correct wire sizes for 
installation, see Table 3. 

NOTICE

 The PENTEK INTELLIDRIVE only 

accepts 230V single phase input power. If 
incoming power does not match this, have a 
qualified electrician alter supply voltage to 
230V/1Ph before connecting it to the Drive. 

Terminal 

Removable 

(pull down)

01+ 01+   I1+ I1-   I2+ I2-   V+  V-   AI+ AI-   P    N    SD CARD

Transducer Cable 

Connections

Submersible Motor:

 3-Ph./ 3-W. 1-Ph., follow colors as above.

Submersible Motor:

 1-Ph./ 2-W., connect to Y and B, any order.

Above-Ground Motors:

 L1 to R, L2 to Y, L3 to B; verify rotation.

 

Output 

Ground Screw

Input Power 
Connections

Input 

Ground Screws

Red

Yellow

Black

Green/Yellow (Ground)

Green/Yellow 

(Ground)

6539 0412

Motor Connections

Red to 

AI

+

Black to 

AI

Green Cable Shield/Screw

Terminal 

Removable 

(pull down)

Figure 9 -  

Basic Wiring Connections 

for Startup

5999 0509

Figure 8 - Pull input and 

motor terminals down to 

remove, making wiring 

easier.

Wiring

 
To allow for ease of wiring, the enclosure 
wiring area is free of electronics other than 
the terminals. Conduit holes and knockouts 
are located so that the wire can be fed straight 
through to the connectors, with minimal 
bending. The terminals accept 1.5mm²-16mm² 
wire. 

For wire sizing refer to table 3, page 6.

 

 

NOTICE

 For convenience in wiring, the input 

and motor terminals unplug from the box. Pull 
them down to remove them for ease of access, 
as shown in Figure 8.
Verify that the terminal connectors are 
completely seated when you replace them. 
It is best practice to connect all output wires 
(larger wire gauge) first, then all input wires.

Pump Connections

 

If the INTELLIDRIVE is used with above ground 

motors not rated for Variable Frequency Drive use, 

maximize motor life by limiting lead length to 8.0m. 

The output of the Drive is single phase (2-wire 

or 3-wire) or 3-phase, depending on motor 

selection during startup.

The output power terminals (motor wire 

connections) are located on the lower right 

side of the Drive and are labeled R (Red), Y 

(Yellow), and B (Black). See Tables 3.

Feed the motor cable through the 20mm conduit 

hole on the bottom right side and into the 

appropriate terminals. If the wire is large enough 

to require a larger conduit hole, remove the 

3.2cm knockout and use the appropriate conduit 

connections. Attach the motor ground wire to 

the grounding screw, located to the upper right 

of the terminal block. Attach the motor power 
wires to the terminals as shown in Figure 9.

NOTICE

 Drive does not sense motor 

temperature and will not protect motor from 
over heating.

Winding

Terminal 

Pentek

Franklin/Pentair Encapsulated 

SAVA

Start/Aux 

R

Red

Black

Brown

Common

Y

Yellow

Brown

Black

Run/Main 

B

Black

Blue/Grey

White

WIRING TABLE FOR OTHER MOTORS

PENTEK IntelliDrive

 Owner’s Manual

PENTEK IntelliDrive

 Owner’s Manual

9

8

Содержание PENTEK INTELLIDRIVE PID2000-1123

Страница 1: ...SSURE CONTROLLER Should the installer or owner be unfamiliar with the correct installation and or operation of this type of equipment please contact the distributor or manufacturer for the correct advice before proceeding with the installation or operation of this product ...

Страница 2: ...age 6 for circuit breaker sizing with no other appliances on the circuit Risk of burns The drive can become hot during normal operation Allow it to cool for 10 minutes after shut down before handling it to avoid burns Risk of electric shock A means for disconnection from the supply mains having a contact separation in all poles must be incorporated in the fixed wiring in accordance with the wiring...

Страница 3: ...gnal The Drive senses and processes the signal in the PID Proportional Integration Derivative control When operating in AUTOSTART mode the Drive increases and decreases the speed of the pump motor as needed to maintain constant pressure in the piping system Keypad The keypad programs the Drive monitors the status of the pump and displays faults if they occur Each button has a unique function as de...

Страница 4: ...984M 5 5 28 1 33 55 88 Mounting the Drive To mount the Drive as shown in Figure 6 follow this procedure 1 First remove the cover by backing out screw at bottom of front cover 2 Push on backplate with thumbs while pulling the cover toward you with index fingers creating a gap See Figures 3 and 4 3 Pull bottom of cover towards you lift up on cover and remove See Figure 5 Gap Figure 3 Separate cover ...

Страница 5: ...ly accepts 230V single phase input power If incoming power does not match this have a qualified electrician alter supply voltage to 230V 1Ph before connecting it to the Drive Terminal Removable pull down 01 01 I1 I1 I2 I2 V V AI AI P N SD CARD Transducer Cable Connections Submersible Motor 3 Ph 3 W 1 Ph follow colors as above Submersible Motor 1 Ph 2 W connect to Y and B any order Above Ground Mot...

Страница 6: ... installed before operating the PENTEK INTELLIDRIVE Most installations will only require the initial startup settings However the installer may need to set additional parameters Information about accessing all parameters explanations of their functions and procedures for changing parameter values will be found later in this section 1 Program the Drive Apply power to the PENTEK INTELLIDRIVE Setup G...

Страница 7: ...9 lists all available commands and parameters for the PENTEK INTELLIDRIVE 6569 0512 Press PSI Preset Use arrows to change the value Press Enter to Save Press Enter Figure 14 Change PSI Setpoint using PSI Preset 6568 0512 Press Auto Start Use arrows to change the value Press Enter to Save Press Enter Verify Running Fixed Press displayed on screen Figure 13 Change PSI Setpoint while running pump Key...

Страница 8: ...VALUE DESCRIPTION DEFAULT MIN MAX Ex Runtime Excessive Runtime Detection _ Enabled Disabled Enabled Enables or disables Excessive Runtime Detection Excessive Runtime Hours Hours 24 1 100 Number of hours Drive can run before it faults on Excessive Runtime Dry Run Auto Restart Delay Minutes 10 Min 3 Min 60 Min Time Drive waits to restart pump when Dry Run is detected Number of Resets 3 0 5 Number of...

Страница 9: ...and 8 Amps at up to 230VAC O1 Output relay dry contacts connection Programmed to close when pump is Running or Faulted Positive wires of an external device See Figures 17 and 18 P Positive connection of an RS 485 communication device see Figure 15 Positive wire from RS 485 device Per RS 485 Standard N Negative connection of an RS 485 communication device see Figure 15 Negative wire from RS 485 dev...

Страница 10: ...n Possible leak Check for pipe break or large leak Dry running pump Check water level in well Ground Fault Ground wire shorted to motor phase Check the ground wire for short to motor phase wire or check insulation integrity with a megger Long motor cable length If motor cable length is more than 305m a reactor or filter may be needed to limit capacitance between motor wires System Not Grounded Ung...

Страница 11: ... Fault Internal voltages are out of range Drive will auto reset and attempt to clear fault Fault Reset can be pressed to clear fault as well Then try to operate pump If fault continues Drive may need replacement Hardware Fault Internal hardware failure Fault Reset can be pressed to clear fault Then try to operate pump If fault continues Drive may need replacement External Fault The external device...

Страница 12: ...rial No Dealer Installer Installer Phone No Date of Installation Wire Lengths in Meters Circuit Breaker to Drive PENTEK INTELLIDRIVE to Motor Supply Voltage Note to Installer Record the data listed above for future reference Give manual to end user or attach to PENTEK INTELLIDRIVE when installation is complete OWNER S INFORMATION PENTEK IntelliDrive Owner s Manual 22 ...

Страница 13: ...yright law Any reproduction display publication modification or distribution is strictly prohibited without the prior written permission from Pentair Disclaimer Pentair reserves the right to change product specifications and products details All product images are for reference purposes only and may not represent actual and or current product 2022 Pentair All rights reserved ...