INITIAL STARTUP
INITIAL STARTUP
Changing a Parameter Value
This procedure works for ANY parameter.
A. Press
MAIN MENU
button.
B. Follow the keypress sequence shown in
Figure 12:
A shorthand way to remember this is:
• Press
ENTER
to change a value
• Press
ENTER
again to save it
• If new value is not saved, any screen change
will result in the loss of the new value.
Table 9 lists all available commands and
parameters for the PENTEK INTELLIDRIVE.
Service Factor Amps
To maximize pump performance, be sure to
enter the correct Service Factor Amps (SF
Amps) in the PENTEK INTELLIDRIVE.
• Entering SF Amps
higher
than the motor
rating lets the Drive supply more amps to
the motor than the motor is designed for
and may allow the motor to overheat (see
Table 8).
• Entering SF Amps
lower
than the motor
rating limits the output amps to less than
the motor is designed for and will reduce
the performance of the pump.
• For any 1-Phase 3-Wire motor, the correct
Service Factor Amp rating for the Drive
is Cap Start/Cap Run amps (see Table 8).
This may not match the motor nameplate,
which (for a Single Phase, 3-Wire motor)
will generally be Cap Start/ Induction Run
Amps.
• For any 3-Phase, 220V or 1 Phase, 2-Wire
motor, use the motor nameplate Service
Factor Amp rating.
NOTICE
PENTEK® submersible motors may
differ from motors of the same horsepower
from other manufacturers.
For 1-Phase,
3-Wire motors from all other submersible
motor manufacturers, enter the motor
manufacturer’s CS/CR service factor amps
for your motor.
For 3-Phase, 220V or 2-Wire
1-Phase motors, use the motor nameplate
amp value. Also see Retro Fit Applications.
Figure 10 - Drive Setup Guide.
Initial Startup and Programming Procedures
Ensure that the cover is installed before
operating the PENTEK INTELLIDRIVE.
Most installations will only require the initial
startup settings. However, the installer may
need to set additional parameters. Information
about accessing all parameters, explanations
of their functions, and procedures for
changing parameter values, will be found later
in this section.
1.
Program the Drive
: Apply power to
the PENTEK INTELLIDRIVE.
Setup Guide
will appear in the display. Follow keypress
sequence shown in Figure 10.
NOTICE
If
Setup Guide does not appear, refer to
Drive Reset Procedure, Figure 20.
6567 0512
Use arrows to
find parameter
Use arrows
to change value
Press Enter
to save
Press Enter
Figure 12 - Changing parameter value.
23.
Pump out well
(if necessary):
Direct pump’s discharge to appropriate
location not connected to system and press
Pump Out.
The pump will run at 45 Hz.
Run the Drive in this mode until the well
discharge runs clear, then press
STOP
button
to stop Drive.
Risk of explosion.
In
Pump Out
mode, pump runs at a constant
speed, which can cause very high pressure if
flow is restricted.
4.
Verify installation:
Make sure that the
system has properly-sized, pressure-relief
valve and pressure tank.
Make sure pressure tank’s precharge is
correct. (See Table 7).
Make sure pump discharge is connected to
system.
5.
System Start:
A. Open valves at the ends of lines so that
air will escape during pressurization.
B. Press
Auto Start;
close valves at the
ends of lines after all air has escaped.
C. The system goes into
Constant Pressure
Operation as soon as the transducer
registers the
Dry Run Sensitivity
parameter
(default is 68 kPa). If system pressure does
not reach that kPa value within 3 minutes,
the Drive will stop. Press
Auto Start again
to restart line fill. If longer priming or
line fill time is required, adjust
Fill Time
parameter. (See Table 9).
PENTEK IntelliDrive
™
Owner’s Manual
PENTEK IntelliDrive
™
Owner’s Manual
11
10