Lengths meet the US National Electrical Code ampacity requirements for either indi
vidual conductors or jac
keted r
ated 75° C cable and can be in conduit or direct
buried. Flat molded and web/ribbon cable are considered jac
keted cable. Refer to NEC
Table 310.15(B)(16) for more information.
Product Specifications · Cable Selection
10
7”, 8” & 10” PENTEK® Submersible Motors
C
ABLE SELECTION
75°C
COPPER C
ABLE SIZE - F
rom Service Entr
ance to Motor (F
eet)
M
OTO
R
AW
G
MCM
V
OL
TS
/Hz
Dia.
HP
KW
FUSE
STD
Dual
Ele
m
en
t
14
12
10
8
6
4
3
2
1
0
00
000
0000
250
300
350
400
500
THREE PHASE
460 V
60 Hz
or
380 V
50 Hz
7”
50
37
200
125
-
-
-
-
-
822
1033
1304
1643
2074
2617
3304
4162
4914
5899
6895
7883
9808
60
45
250
150
-
-
-
-
-
-
849
1072
1351
1705
2151
2715
3421
4039
4848
5668
6480
8062
8”
40
30
175
100
-
-
-
-
620
989
1243
1570
1978
2497
3151
3977
5011
5916
7102
8301
9491
50
37
200
125
-
-
-
-
-
822
1033
1304
1643
2074
2617
3304
4162
4914
5899
6895
7883
9808
60
45
250
150
-
-
-
-
-
-
848
1071
1349
1703
2148
2712
3416
4033
4842
5660
6471
8051
75
55
300
175
-
-
-
-
-
-
-
888
1119
1412
1781
2249
2833
3345
4015
4694
5366
6677
100
75
450
250
-
-
-
-
-
-
-
-
-
-
1305
1648
2076
2451
2942
3439
3932
4892
125
92
500
300
-
-
-
-
-
-
-
-
-
-
-
1327
1672
1974
2370
2771
3168
3941
10”
150
110
601
350
-
-
-
-
-
-
-
-
-
-
-
-
1416
1671
2007
2346
2682
3336
175
129
700
400
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1750
2045
2338
2909
200
147
800
450
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1794
2051
2552
250
185
1000
601
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2028