P/N 474131 Rev. M 8/2020 MasterTemp Pool and Spa Heater
43
SAFETY CONTROLS,
(continued)
OPERATION OF IGNITION MODULE
The Ignition Module
,
(see Figure 43),
is microprocessor based and operates on 24VAC supplied by the transformer. The
control utilizes a microprocessor to continually and safely monitor, analyze, and control the proper operation of the gas
flame holder. The module with the presence of the flame sensor, using flame rectification, allows the heater to operate.
WARNING
Diagnostic errors are displayed on
the control panel LCD: PS, HLS, SFS,
AFS, AGS, IGN, or NONE.
See Troubleshooting (page 51-53)
Flame Current
Check Point
Figure 43.
Diagnostic Indicator
(See table below)
Displayed Message
Description
CONTROL FAULT
Displays Message on Automation System
AIR FLOW FAULT
Displays Message on Automation System
FLAME NO CALL FOR HEAT
Displays Message on Automation System
IGNITION LOCKOUT
Displays Message on Automation System
WEAK FLAME
Displays Message on Automation System
and viewed on Heater menu
GOOD FLAME
Displays Message on Automation System
and viewed on Heater menu
ERROR PS MESSAGE
• The ERR PS message on the LCD indicates that there is insufficient water flow to the heater. If the pump is
operating, this usually indicates that the filter and/or skimmers should be cleaned (some filters may require
back-washing). If the message remains on after the filter/skimmers have been serviced, the system should be
checked by a qualified service technician.
RISK OF EXPLOSION OR FIRE CAUSING BURNS OR DEATH IF SAFETY INTERLOCKS ARE DISABLED. DO NOT attempt to operate
heater when The ERR HLS, ERR AFS, ERR IGN, ERR AGS, ERR SFS, E01, E05, E06, 126 messages on the LCD indicates a fault in the
heater or its controls. If any of these messages are displayed, shut down the heater (See “TO TURN OFF GAS TO THE APPLIANCE”
on page 41), and have a qualified service technician check the system.
Table 9. Diagnostic Indicator
Section 2. Operations