FLECK
3150 Downflow Service Manual
•
7
3. The black center knob will make one revolution in the
following approximately three hours and stop in the
position shown in the drawing.
4. Even though it takes three hours for this center knob to
complete one revolution, the regeneration cycle of your
unit might be set for only one half of this time.
5. In any event, conditioned water may be drawn after rinse
water stops flowing from the water conditioner drain line.
Immediate Regeneration Timers
These timers do not have a 24 hour gear. Setting the gallons
on the program wheel and manual regeneration procedure
are the same as previous instructions. The timer will
regenerate as soon as the capacity gallons reaches zero.
NOTE:
The program wheel to the left may be different than
the program wheel on the product.
NOTE:
To set meter capacity rotate manual knob one - 360°
revolution to set gallonage.
61502-3200 Rev A
Figure 3
3200, 3210, 3220, 3230 REGENERATION
CYCLE SETTING PROCEDURE
How To Set The Regeneration Cycle Program
The regeneration cycle program on your water conditioner
has been factory preset, however, portions of the cycle or
program may be lengthened or shortened in time to suit
local conditions.
3200 Series Timers (Figure 4)
1. To expose cycle program wheel, grasp timer in upper
left-hand corner and pull, releasing snap retainer and
swinging timer to the right.
2. To change the regeneration cycle program, the program
wheel must be removed. Grasp program wheel and
squeeze protruding lugs toward center, lift program wheel
off timer. Switch arms may require movement to
facilitate removal.
3. Return timer to closed position engaging snap retainer in
back plate. Make certain all electrical wires locate above
snap retainer post.
Timer Setting Procedure
How To Change The Length Of The Backwash Time
The program wheel as shown in the drawing is in the service
position. As you look at the numbered side of the program
wheel, the group of pins starting at zero determines the
length of time your unit will backwash.
For example, if there are six pins in this section, the time
of backwash will be 12 min. (2 min. per pin). To change the
length of backwash time, add or remove pins as required.
The number of pins times two equals the backwash time in
minutes.
How To Change The Length Of Brine And Rinse Time
1. The group of holes between the last pin in the backwash
section and the second group of pins determines the
length of time that your unit will brine and rinse (2 min.
per hole).
2. To change the length of brine and rinse time, move the
rapid rinse group of pins to give more or fewer holes in
the brine and rinse section. Number of holes times two
equals brine and rinse time in minutes.
How To Change The Length Of Rapid Rinse
1. The second group of pins on the program wheel
determines the length of time that your water conditioner
will rapid rinse (2 min. per pin).
2. To change the length of rapid rinse time, add or remove
pins at the higher numbered end of this section as
required. The number of pins times two equals the rapid
rinse time
in minutes.
How To Change The Length Of Brine Tank Refill Time
1. The second group of holes in the program wheel
determines the length of time that your water conditioner
will refill the brine tank (2 min. per hole).
2. To change the length of refill time, move the two pins at
the end of the second group of holes as required.
3. The regeneration cycle is complete when the outer
microswitch is tripped by the two pin set at end of the
brine tank refill section.
4. The program wheel, however, will continue to rotate until
the inner micro switch drops into the notch on the
program wheel.
61502-3210 Rev A
Содержание FLECK3150 DOWNFLOW
Страница 1: ...waterpurification pentair com FLECK 3150 DOWNFLOW SERVICE MANUAL...
Страница 8: ...8 FLECK 3150 Downflow Service Manual 37 615023200 Rev A 3200 TIME CLOCK TIMER ASSEMBLY 36 38...
Страница 10: ...10 FLECK 3150 Downflow Service Manual 3210 METER DELAYED TIMER ASSEMBLY 41 42 61502 3210 Rev A 40 43...
Страница 30: ...30 FLECK 3150 Downflow Service Manual FLOW DATA INJECTOR DRAW RATES TR20395...