background image

SYSTEM DEFINITIONS

System 

Number

System 

Description

# of 

Tanks/

Controls

Type

Operation Discussion

4

Single Unit

1

Time Clock: No Meter

Immediate: One Meter

Delayed: One Meter

Remote Signal Start: No Meter

Single tank configuration. 

5

Interlocked

2, 3, or 4

Immediate: All Meters

Remote Signal Start: No Meter

All tanks in parallel supplying treated water. Each unit in the system 

will have its own flow meter/sensor input. The control will delay the 

start of Regeneration if another unit is already in Regeneration. Once 

that unit has completed a Regeneration cycle, and has returned to 

Service,the unit with longest regeneration queue time will begin 

Regeneration. No more than one unit will be in Regeneration at a time.

6

Series 

Regeneration

2, 3,  or 4

Immediate: One Meter

Delayed: One Meter

Remote Signal Start: No Meter

All tanks in parallel supplying treated water. Only #1 control will 

monitor flow meter/sensor input. When a regeneration is required 

for the system, it will regenerate valve address #1 first, immediately 

followed by #2, then #3, then #4 if installed. No more than one unit 

will be in Regeneration at a time.

7

Twin 

Alternating

2

Immediate: One Meter

Remote Signal Start: No Meter

One tank online supplying treated water, one tank in Standby. Only 

#1 control will monitor its flow meter/sensor input. Regeneration of 

a unit will begin after the other control has left Standby and returned 

to Service. When the Regeneration cycle is complete, the regenerated 

unit will enter Standby. Standby on each tank is controlled by the 24 

VAC solenoid bypass on the NXT circuit board.

9

Multiple Tank 

Alternating

2, 3, or 4

Immediate: All Meters

Remote Signal Start: No Meter

One, two, or three tanks online supplying treated water, one tank in 

Standby. Meter/sensor input is required on each tank. Regeneration of 

a unit will begin after the other control has left Standby and returned 

to Service. When the Regeneration cycle is complete, the regenerated 

unit will enter Standby. Standby on each tank is controlled by the 24 

VAC solenoid bypass on the NXT circuit board.

TIMER OPERATION

Timer Operation During Programming

The timer enters the Program Mode in Standby or Service 

Mode as long as it is not in regeneration. While in the Program 

Mode the timer continues to operate normally monitoring 

water usage. Timer programming is stored in memory 

permanently.

Timer Operation During A Power Failure

All program settings are stored in permanent memory. Current 

valve position, cycle step time elapsed, and time of day are all 

stored during a power failure. These settings will be restored 

upon power re-application. Time is kept during a power failure, 

and time of day is adjusted upon power up (as long as power is 

restored within 12 hours).

NOTE: The time of day on the main display screen will flash 

for 5 minutes when there has been a power outage. 

The flashing of the time of day can be stopped by 

pressing any button on the display.

Remote Lockout 

The timer does not allow the unit/system to go into 

Regeneration until the Regeneration Lockout Input signal to 

the unit is cleared. This requires a contact closure to activate 

the unit. The recommended gauge wire is 20 with a maximum 

length of 500 feet.

Regeneration Day Override Feature 

If the Day Override option is turned on and the valve reaches the 

set Regeneration Day Override value, the Regeneration Cycle 

starts if no other networked unit is in Regeneration. If other 

units are in regeneration, it is added to a regeneration queue. 

This occurs regardless of the remaining volume available.

WARNING:

 Transformer must be grounded and ground 

wire must be terminated to the circuit board 

grounding screw before installation. Supplied 

40VA transformer must be used.

TIMER DISPLAY FEATURES

Shift Button

Adjusts Values to the Left

Up Button

Adjusts Values Up

Volume Remaining

Status LED

Diagnostic Button

View Flow Rate, Peak Flow 

Rate, Totalizer, Hours 

Between Last Two 

Regenerations, Hours Since 

Last Regeneration, Adjustable 

Volume Remaining, Valve 

Position, Send & Receive 

Errors, Software Version

Extra Cycle Button

Cycle Valve in 

Regeneration/Cycle 

Programming Steps

System

Number

Valve

Address

Valve State

(INI, RGQ, SRV, LCK)

Flow

Indicator

Time

of Day

Display Screen

Time of Day alternates 

with Error Screen 

Example: Valve #, Volume 

Remaining, Errors

Down Button

Adjusts Values Down

Figure 5 

6 • 

FLECK

 7000 NXT Service Manual

Содержание Fleck 7000 NXT

Страница 1: ...FLECK 7000 NXT SERVICE MANUAL...

Страница 2: ...System installation requires information from a number of suppliers not known at the time of manufacture This product should be installed by a plumbing professional This unit is designed to be install...

Страница 3: ...and place the control valve on the tank 6 All soldering MUST be done on any connections requiring soldering prior to connecting the main control valve The main control valve will be damaged if it is c...

Страница 4: ...cted to the 24 VAC Bypass Relay terminal strip on the lower left portion of the NXT circuit board Figure 6 7000NXT Circuit Board Plastic solenoid operated diaphragm valves are sold separately from the...

Страница 5: ...re 3 Interlocked Multiple Tank Alternating Systems Systems 5 and 9 BRINE TANK RESIN TANK DRAIN LINE INLET OUTLET BALL VALVE OUTLET SHUTOFF SOLENOID OPERATED DIAPHRAGM VALVE BRINE LINE BALL VALVE INLET...

Страница 6: ...peration During Programming The timer enters the Program Mode in Standby or Service Mode as long as it is not in regeneration While in the Program Mode the timer continues to operate normally monitori...

Страница 7: ...will display on the screen when flow is going through the meter TIMER DISPLAY SCREEN EXAMPLES 1 In Service System 4 Time Clock 4 SRV 03 45PM REGEN IN 07 DAYS 2 In Service System 4 Flow Meter Initiate...

Страница 8: ...c c c c c c c c c c c c Chemical Pump x x x x x x u u x x x x CPO Aux Relay Volume c c c c c c c c c c c c 1 999 gallons 00 1 99 9 liters CPO Aux Relay Time c c c c c c c c c c c c 00 00 01 02 00 00 0...

Страница 9: ...NOTE In U S Gallons mode the display will be in 12 hour time Example Grains Default Example 00 Default Filter Iron Filter Do Not Use Options 00 06 00 Default Range 1 second to 99 minutes 1 hour 39 min...

Страница 10: ...s some displays cannot be viewed or set Entering Master Programming Mode 1 Press and hold the Shift and Up buttons for 5 seconds OR 2 Set the time of day display to 12 01 PM or 12 01HR See the Setting...

Страница 11: ...ing 1 Use Up or Down buttons to adjust this value 2 Press the Extra Cycle button 9 Unit Capacity This program selects the individual timer s total capacity of hardness that can be removed The unit cap...

Страница 12: ...uring Regeneration only The second turns the output On during Service only every time a set volume of water used has accumulated MASTER PROGRAMMING GUIDE continued 16 Timed Auxiliary Relay Output Wind...

Страница 13: ...this value 3 Press the Extra Cycle button 20 Pulses per Gallon Liter This program step sets the pulses per gallon liter for generic flow meters 1 Press the Shift button to select the digit you want to...

Страница 14: ...n Press the Shift Up and Down buttons to move the cursor and change the value of the numbers Press the Extra Cycle button to proceed to the next step 5 Regeneration Time Press the Shift Up and Down bu...

Страница 15: ...zer The total volume of treated water that passes through a meter will be counted NOTE The user cannot edit below the current volume remaining 1 Reset to zero by holding the Up and Down arrow keys for...

Страница 16: ...w Phil Rd Hd 6 32 x 5 16 12 1 12473 Screw Hex Wsh 10 24 x 5 8 13 2 11805 Screw Rd Hd 4 40 x 5 8 Type 1 14 1 61920 01 Transformer Assy 7000NXT 40VA US 61920 02 Transformer Assy 7000NXT 40VA Japan 61920...

Страница 17: ...mblies 10 1 61XXX DLFC Assemblies 11 1 43776 O ring 021 7000 CSTM 12 2 13302 01 O ring 014 560CD 13 1 40946 Clip Brine Retaining 14 1 40945 Clip Drain Retaining 15 1 40950 Screen Injector 7000 16 1 40...

Страница 18: ...y 1 1 4 NPT w O ring 40565 11 Connector Assy 1 1 4 BSP w O ring 3 2 41242 01 Connector Assy 1 1 4 Sweat w O ring 41243 01 Connector Assy 1 1 4 1 1 2 Sweat w O ring 4 2 40576 Clip H Plastic 7000 5 1 40...

Страница 19: ...em No QTY Part No Description 1 1 60014 Safety Brine Valve Assy 2310 2 1 60068 30 Float Assy 2310 w 30 Rod 3 1 60002 34 Air Check 500 2310 SAFETY BRINE VALVE 42112 Rev A FLECK 7000 NXT Service Manual...

Страница 20: ...ce the error condition is corrected all units return to the operating status they were in prior to the error and regeneration is queued according to the normal system operation If reprogramming the un...

Страница 21: ...re the units on the network are not configured the same as 1 the Lead unit Exceed Unit Size DETECTED ERROR EXCEED UNIT SIZE 1 There are more units on the system than the Lead is programmed for Matchin...

Страница 22: ...Check for dry well condition Improperly sized drain line flow control Check for proper drain rate Iron in conditioned water Fouled mineral bed Check backwash brine draw and brine tank fill Increase f...

Страница 23: ...WATER CONDITIONER FLOW DIAGRAMS In Service Position 40988 Rev A 41121 Rev A Backwash Position 40988 Rev A 41121 Rev A FLECK 7000 NXT Service Manual 23...

Страница 24: ...Brine Position 40988 Rev A 41121 Rev A WATER CONDITIONER FLOW DIAGRAMS continued Slow Rinse Position 40988 Rev A 41121 Rev A 24 FLECK 7000 NXT Service Manual...

Страница 25: ...Second Backwash Position 40988 Rev A 41121 Rev A WATER CONDITIONER FLOW DIAGRAMS continued Rapid Rinse Position 40988 Rev A 41121 Rev A FLECK 7000 NXT Service Manual 25...

Страница 26: ...ver turn the cycle cam counter clockwise to the position shown in the illustration above 3 Remove brine cam if equipped 4 Slightly pull the two tabs outward and push the gearbox slightly upward to rem...

Страница 27: ...A Figure 10 After the circuit board is installed 1 Connect the motor wires to the motor connector on the circuit board 2 Connect the transformer cable to the transformer connector on the circuit board...

Страница 28: ...DIMENSIONAL DRAWINGS 61500 7000XTR LNE Rev A 28 FLECK 7000 NXT Service Manual...

Страница 29: ...METER FLOW DATA TR18753 Softener TR18688 Filter 41140 02 Rev A 7000NXT VALVE FLECK 7000 NXT Service Manual 29...

Страница 30: ...INJECTOR FLOW DATA TR18755 Rev B 30 FLECK 7000 NXT Service Manual...

Страница 31: ...3 5 GPM 61455 40 DLFC 3 4 4 0 GPM 61455 45 DLFC 3 4 4 5 GPM 61455 50 DLFC 3 4 5 0 GPM 61455 60 DLFC 3 4 6 0 GPM 61455 70 DLFC 3 4 7 0 GPM 61456 00 DLFC 1 Blank 61456 8 0 DLFC 1 8 0 GPM 61456 9 0 DLFC...

Страница 32: ...rks and logos are the property of their respective owners Because we are continuously improving our products and services Pentair reserves the right to change specifications without prior notice Penta...

Отзывы: