background image

SYSTEM DISINFECTION

Disinfection of Water Softeners

The materials of construction of the modern water softener 

will not support bacterial growth, nor will these materials 

contaminate a water supply. During normal use, a softener 

may become fouled with organic matter, or in some cases with 

bacteria from the water supply. This may result in an off-taste or 

odor in the water.

Some softeners may need to be disinfected after installation and 

some softeners will require periodic disinfection during their 

normal life. 

Depending upon the conditions of use, the style of softener, the 

type of ion exchanger, and the disinfectant available, a choice 

can be made among the following methods.

Sodium or Calcium Hypochlorite

Application

These materials are satisfactory for use with polystyrene resins, 

synthetic gel zeolite, greensand and bentonites.

5.25% Sodium Hypochlorite

These solutions are available under brands names of household 

bleach. If stronger solutions are used, such as those sold for 

commercial laundries, adjust the dosage accordingly.

Dosage

A.  Polystyrene resin; 1.2 fluid ounce (35.5 ml) per cubic foot.

B. 

Non-resinous exchangers; 0.8 fluid ounce (23.7 ml) per 

cubic foot.

1.  Salt tank softeners

A.  Backwash the softener and add the required amount of 

hypochlorite solution to the well of the salt tank. The salt 
tank should have water in it to permit the solution to be 
carried into the softener.

B. 

Proceed with the normal recharge.

Calcium Hypochlorite

Calcium hypochlorite, 70% available chlorine, is available in 

several forms including tablets and granules. These solid 

materials may be used directly without dissolving before use.

1.  Dosage

A.  Two grains (approximately 0.1 ounce [3 ml]) per cubic 

foot.

2.  Salt tank softeners

A.  Backwash the softener and add the required amount of 

hypochlorite to the well of the salt tank. The salt tank 
should have water in it to permit the chlorine solution to 
be carried into the softener.

B. 

Proceed with the normal recharge.

START-UP INSTRUCTIONS/ 
FLUSHING & CONDITIONING

The water softener should be installed with the inlet, outlet, and 

drain connections made in accordance with the manufacturer’s 

recommendations, and to meet applicable plumbing codes.

1. 

Program the valve control according to instructions shown in 
this manual.

2. 

Start an immediate regeneration by holding the Extra Cycle 
button for five seconds. Position the valve to backwash. 
Ensure the drain line flow remains steady for 10 minutes or 
until the water runs clear.

3. 

Position the valve to the brine draw/slow rinse position. 
Ensure the unit is drawing water from the brine tank (this 
step may need to be repeated).

4. 

Position the valve to the rapid rinse position. Check the drain 
line flow, and run for five minutes or until the water runs 

clear.

5. 

Position the valve to the start of the brine tank fill cycle. 
Ensure water goes into the brine tank at the desired rate. 
The brine valve drive cam will hold the valve in this position 
to fill the brine tank for the first regeneration.

6. 

Replace control cover.

7. 

Put salt in the brine tank.

 

NOTE: Do not use granulated or rock salt.

4

 • 

PENTAIR FLECK 5000 Control Valve Service Manual

Содержание FLECK 5000

Страница 1: ...pentair com FLECK 5000 CONTROL VALVE SERVICE MANUAL...

Страница 2: ...0626 18 Paddle Meter Assembly P N 60086 50 18 Bypass Valve Assembly Metal 19 Bypass Valve Assembly Plastic 19 Safety Brine Valve 20 Dimensional Drawings 21 Water Conditioner Flow Diagrams 22 Injector...

Страница 3: ...Outside Faucet Bath Tub Lavatory Toilet Kitchen Laundry Tubs Pump or Meter Hot Water Outlet Water Heater Brine Tank Overflow Drain Optional Floor Drain Drain Line Bypass Softener Grounding Strap Figur...

Страница 4: ...hypochlorite 70 available chlorine is available in several forms including tablets and granules These solid materials may be used directly without dissolving before use 1 Dosage A Two grains approxima...

Страница 5: ...13 mm Backwash flow rates in excess of 7 gpm 26 5 Lpm or length in excess of 20 feet 6 m require 3 4 inch 19 mm drain line Commercial drain lines should be the same size as the drain line flow control...

Страница 6: ...Indicator Service Icon Programming Icon Extra Cycle Button Up Button Down Button Error Information Icon Features of the SXT Power backup that continues to keep time and the passage of days for a mini...

Страница 7: ...normal operation Pressing the Extra Cycle button during a regeneration cycle immediately advances the valve to the next cycle step position and resumes normal step timing Control Operation During Pro...

Страница 8: ...ety Factor Percentage of the system capacity to be used as a reserve RC Fixed Reserve Capacity Fixed volume to be used as a reserve DO Day Override The system s day override setting RT Regen Time The...

Страница 9: ...n entering Master Programming Mode The Display Format setting specifies the unit of measure that will be used for volume and how the control will display the Time of Day This option setting is identif...

Страница 10: ...MING MODE CONTINUED 9 Safety Factor Display Code SF Press the Extra Cycle button Use this display to set the Safety Factor This setting specifies what percentage of the system capacity will be held as...

Страница 11: ...ion for each day Use the Up and Down buttons to adjust the setting as needed Press the Extra Cycle button to accept the setting and move to the next day Note that the control requires at least one day...

Страница 12: ...ds while in service and the time of day is NOT set to 12 01 PM 2 Use this display to adjust the Day Override This option setting is identified by DO in the upper left hand corner of the screen 3 Press...

Страница 13: ...in service 2 Press the Up button Use this display to view the current Flow Rate This option setting is identified by FR in the upper left hand corner of the screen 3 Press the Up button Use this disp...

Страница 14: ...r Downflow Softener U S Power Supply 1 Injector 0 50 GPM BLFC 500006 003 Turbine Meter B W Filter U S Power Supply NOTE NOTE Above part numbers DO NOT include the following parts Bypass Assembly Conne...

Страница 15: ...sher Head 10 24 0 81 9 1 13304 O ring 121 10 1 18303 01 O ring 336 560CD 11 1 13030 Retainer Distributor Tube O ring 12 1 18569 Retainer Tank Seal 13 1 18312 DLFC Housing Retainer Clip 14 1 60115 001...

Страница 16: ...4 Yoke SS NPT Washers 19153 Washer Flow 0 6 GPM 19152 Washer Flow 0 8 GPM 12085 Washer Flow 1 2 GPM 19150 Washer Flow 1 3 GPM 12086 Washer Flow 1 5 GPM 12087 Washer Flow 2 0 GPM 12088 Washer Flow 2 4...

Страница 17: ...REQUIREMENT CHECKED 20 16 13 14 14 15 15 11 10 9 2 5 12 8 4 3 2 1 6 17 18 7 272481 A RELEASE FOR PRE PRODUCTION 44553 00 5000 44553 01 50DP 12 9 12 PWS ITEM NO PART NUMBER DESCRIPTION 44553 00 QTY 445...

Страница 18: ...Item No QTY Part No Description 1 1 14716 Meter Cap Assy NT includes items 2 3 and 4 2 1 13874 Cap Meter Electronic 3 1 13847 O ring 137 Std Meter 4 1 17798 Screw Slot Hex Washer Head 5 1 19121 01 Met...

Страница 19: ...Yoke 1 BSP Plastic 41027 02 Yoke 3 4 BSP Cast Machined 18706 12 Yoke 3 4 BSP Plastic 19620 01 Yoke Assy 3 4 R Angle 90 Deg 6 1 60049 Bypass Plastic Not Shown 2 19228 01 Adapter Assy Coupling w O ring...

Страница 20: ...9647 Elbow Safety Brine Valve 9 2 19625 Nut Assy 3 8 Plastic 10 1 18312 Retainer Drain 11 1 60014 Safety Brine Valve Assy 2310 12 2 10150 Grommet 0 30 Dia 13 1 60068 30 Float Assy 2310 w 30 Rod 14 1 6...

Страница 21: ...DIMENSIONAL DRAWINGS PENTAIR FLECK 5000 Control Valve Service Manual 21...

Страница 22: ...neral in the mineral tank Conditioned water enters center tube through the bottom distributor then flows up through the center tube and to the outlet of the valve Hard water enters unit at valve inlet...

Страница 23: ...ough nozzle and throat down through mineral and enters the center tube through bottom distributor and out through the drain line Hard water flows from inlet around the piston down through the mineral...

Страница 24: ...TR18755 Rev B 24 PENTAIR FLECK 5000 Control Valve Service Manual INJECTOR FLOW DATA...

Страница 25: ...BLACK ORANGE WT BLK BLACK WHITE GREEN BLUE BLUE WHITE BLUE WHITE BLUE PURPLE ORANGE BLACK WT BLK YELLOW BLACK BROWN METER P1 S N N H S VDO P2 N O H PWR H S CB1 50 60 HZ CB1 SXT Timer T1 24V Transforme...

Страница 26: ...upport pentair com PENTAIR COM All indicated Pentair trademarks and logos are property of Pentair Third party registered and unregistered trademarks and logos are the property of their respective owne...

Отзывы: