NGC-20 INSTALLATION MANUAL
8
Communications
Physical network
RS-485 and Class 1 Bluetooth
Protocol / topology
ModBus RTU or ASCII. Multi drop / Daisy chain
Cable and maximum length
Shielded twisted pair cable, 0.5 mm² (AWG 24) or larger.
Maximum cable length between should be no more than 1200 m.
Maximum quantity of controllers in
Max. of 247 units per NGC-UIT or per communication port
one network
(ModBus) Network address
Software programmable via DigiTrace NGC-CMA-NH or DigiTrace NGC-CMA-EX
Programming and setting
Method
Through handheld programming device DigiTrace NGC-CMA and a wireless Bluetooth
connection or via RS485 interface and DigiTrace Supervisor software or DigiTrace User
Interface Terminal (DigiTrace NGC-UIT-ORD, DigiTrace NGC-UIT-OUT) and customized
DigiTrace software.
Units of measure
°C or °F, software selectable.
Memory
Nonvolatile. There is no loss of parameters after the event of power outage or long term
shut down. Data holding time ~10 years.
LED indicators
Status LEDS are available for:
NGC-20-C-E
Heater, Alarm, RS485 communication, Bluetooth communication
NGC-20-CL-E
Heater, Alarm, Limiter (tripped), RS485 communication and Bluetooth.
measuring ranges
Temperature range controller
From –80°C to +700°C in steps of 1K
Temperature range limiter
From –60°C to +599°C in steps of 1K (NGC-20-CL-E only)
Voltage
From 50 VAC to 305 VAC
Load Current
From 0.3 A to 30 A
Ground fault current
From 10 mA to 250 mA
Heater Time Alarm
From 1 to 1x 10
6
hours
Relay Cycle Alarm
From 0 to 2x 10
6
operations
ordering information
DigiTrace nGC-20 control units
Product name
DigiTrace NGC-20-C-E (Standard temperature control unit)
Part number & (weight)
1244-007035
(3.3 kg.)
Product name
DigiTrace NGC-20-CL-E (Temperature control unit with integrated temperature limiter)
Part number & (weight)
1244-007036
(3.4 kg.)