5

Pump
Operations

8.  Turn switches to Auto position,

and pumps should start and 
op 

er 

ate together until level

drops to turn-off point.

9.  Repeat this operation cycle

sev 

er 

al times before leaving

the job.

10.Check voltage when pumps 

are operating, and check the
amp draw of each pump.
Check amps on each wire as
sometimes a high leg will
exist. One leg can be 
some 

what higher by 5 to 10

per cent without causing trouble.
For excessive amp draw on
one leg, the electric utility
company should be consulted.

WARNING: Before handling
these pumps and controls, always
dis con nect  the  pow er  first.

Do not smoke or use sparkable
elec tri cal devices or flames in a
septic (gaseous) or possible 
septic sump.

Field Service on Hydromatic
Hazardous Location Pumps:

If a Hydromatic hazardous
location pump is used in a
hazardous location the pump must
be returned to the factory for
service.  This will ensure the
integrity of the hazardous location
rating of the pump and com 

ply

with our warranty re 

quire 

ments. 

Pumps out of warranty and not
used in a hazardous location can
be field serviced by any reputable
serviceman. When any field 
servicing is per formed on a pump,
the  fol low ing  in struc tions  should
be followed care ful ly.

Disconnecting Pump Cords:

If a Hydromatic hazardous
location pump is to be removed
from its lo ca tion, one of two ways
may be used to disconnect the
pump cords from the rest of the
system.

Pump cords may be disconnected
at control panel (on sump mounted
con trol panels) and cord as sem bly
taken with pump.

CAUTION: If cord openings
from sump to con trol panel are
open, gas 

es from sump could

enter panel and an explosive
condition could ex ist.

Pump cords may be disconnected
at pump by removing the cord and
cap assembly, unplugging sensor
wires, and re mov ing wire nuts.

After removal from pump, 
reinstall wire nuts in cord and cap
assembly and install protective
cover.

CAUTION: Do not reconnect
pow 

er to a cord and cap

assembly while removing from
pump.

Replacing Cords:

The power cord and heat 
sensor - seal failure cord is potted
into the con 

nec 

tion box cap,

forming

the cord and cap

assembly.

If cords require replacement due
to damage or cords being too
short, cord and cap assembly
must be replaced as a complete
assembly avail able from factory.

1. 

 

Remove cord and cap
assembly

from 

con nec tion

box.

2.  Disconnect wires taking note

of color/num ber coding.

3.  Connect wires of new cord

and cap as sem bly in the same
manner as the old one was
removed.

4. 

 

Check for moisture and
dryout.

5.  Reinstall cord and cap assembly

on con nec tion box taking care
not to pinch wires.

6. 

 

Check pump for proper 
rotation before re 

turn 

ing to

normal service.

Replacing Stator:

If motor winding is burned or
shorted, it can be rewound or
replaced with new factory wound
sta tor. Refer to sectional drawing
of pump and motor, and use the
following steps to remove and
replace stator.

As the motors are oil filled, no
lubrication or other main 

te 

nance

is re quired.

If the heat sensor and seal failure
are hooked up properly, no 
attention is necessary as long as
the seal failure indicator light
doesn’t come on. To ensure 
continuity of the seal sensor leads,
a test light is provided on 
in trin si cal ly 

safe 

Hydromatic 

panels as standard equipment.

Pump should be checked every
quar ter for cor ro sion and wear.

Servicing Instructions:

IMPORTANT: Read all 
directions before replacing 
any parts.

Pump
Maintenance

Содержание Hydromatic H3HX Series

Страница 1: ...D FM 06 10 Item E 03 487 Part 5625 487 1 NOTE To the installer Please make sure you provide this manual to the owner of the equipment or to the responsible party who maintains the system Installation...

Страница 2: ...hazardous location submersible pumps have two factory installed moisture detectors seal failure probes They are in a normally open series circuit in the seal chamber Under normal operating conditions...

Страница 3: ...A When using single phase pumps make sure red pump lead is connected to capacitor circuit connect amprobe to pump power cord and turn pump on Pump will show high amp draw momentarily then as pump come...

Страница 4: ...RED 330K D C GREEN HEAT SENSORS 120 VAC 5A SEAL PROBES 300 VAC 20 MA POWER CORD CONTROL CORD SEE TYPICAL CONTROL CIRCUITRY BELOW CRS RUN CAPACITOR CRS START CAPACITOR CAPACITOR PACK PANEL M RUN LIGHT...

Страница 5: ...could enter panel and an explosive condition could exist Pump cords may be disconnected at pump by removing the cord and cap assembly unplugging sensor wires and removing wire nuts After removal from...

Страница 6: ...O ring seal has been replaced If O ring is nicked or cut replace with new ring This applies to all O rings used in assembly 11 After all leads are reconnected in the connection box make a high voltage...

Страница 7: ...Locktite red on socket head locking screw in end of shaft 12 Before refilling chamber with oil air test as described in replacing stator 13 Refill both chambers with oil as described in replacing stat...

Страница 8: ...art No No Description Qty Ref Part Part No No Description Qty PUMP PUMP V RPM Connection Rotor Stator Connector box Spacer Connector Connector DESCRIPTION PART HP Box B1 Shaft Assy B2 B3 to cord cap B...

Страница 9: ...9 H3HX...

Страница 10: ...perly install operate or maintain the unit in accordance with the printed instructions provided b to failures resulting from abuse accident or negligence c to normal maintenance services and parts use...

Страница 11: ......

Страница 12: ...Line Voltage _________________________________Actual ___________________________________ Voltage to Pumps _____________________________________Actual ___________________________________ Type of Junct...

Отзывы: