background image

4

5

WHITE

BLACK

PINK

L1

L3

A

B

120 VAC

FUSE

M

TYPICAL THREE PHASE

MOTOR CONNECTIONS

O/L

O/L

L2

O/L

FUSES

GREEN

RED

WHITE

BLACK

PUMP MOTOR

F

E

RED

330K

D

C

GREEN

HEAT SENSORS

120 VAC, 5A

SEAL PROBES

300 VAC, 20 MA

POWER

CORD

CONTROL

CORD

SEE TYPICAL CONTROL

CIRCUITRY BELOW

WHITE

BLACK

PINK

L1

A

B

120 VAC

M

TYPICAL FM ONLY SCHEMATICS

TYPICAL SINGLE PHASE

MOTOR CONNECTIONS

O/L

O/L

L2

FUSES

GREEN

RED

BLACK

WHITE

PUMP MOTOR

F

E

RED

330K

D

C

GREEN

HEAT SENSORS

120 VAC, 5A

SEAL PROBES

300 VAC, 20 MA

POWER

CORD

CONTROL

CORD

SEE TYPICAL CONTROL

CIRCUITRY BELOW

CRS

RUN

CAPACITOR

CRS

START

CAPACITOR

CAPACITOR

PACK PANEL

M

RUN

LIGHT

SEAL

FAILURE

INDICATOR

D

C

TO SEAL PROBES

IN PUMP MOTOR

SEAL

FAILURE

RELAY

LEVEL

CONTROL

CIRCUITRY

H

O

A

H

A

R

OVERLOADS

CAPACITORS AND/OR CONTROLS SHOULD BE LOCATED OUTSIDE
HAZARDOUS AREA AND ENCLOSED IN AN APPROPRIATE ENCLOSURE.

NOTE: 

TYPICAL

CONTROL

CIRCUITRY

SEE TYPICAL

CONTROL CIRCUITRY

BELOW

DUAL VOLTAGE

3 PHASE MOTOR WIRING

230V  3ø

460V  3ø

GREEN

GREEN

R

(L3)

W

(L2)

BL

(L1)

R

(L3)

W

(L2)

BL

(L1)

1

2

3

7

8

9

4

5

6

1

2

3

7

8

9

4

5

6

Содержание Hydromatic H3HX Series

Страница 1: ...D FM 06 10 Item E 03 487 Part 5625 487 1 NOTE To the installer Please make sure you provide this manual to the owner of the equipment or to the responsible party who maintains the system Installation...

Страница 2: ...hazardous location submersible pumps have two factory installed moisture detectors seal failure probes They are in a normally open series circuit in the seal chamber Under normal operating conditions...

Страница 3: ...A When using single phase pumps make sure red pump lead is connected to capacitor circuit connect amprobe to pump power cord and turn pump on Pump will show high amp draw momentarily then as pump come...

Страница 4: ...RED 330K D C GREEN HEAT SENSORS 120 VAC 5A SEAL PROBES 300 VAC 20 MA POWER CORD CONTROL CORD SEE TYPICAL CONTROL CIRCUITRY BELOW CRS RUN CAPACITOR CRS START CAPACITOR CAPACITOR PACK PANEL M RUN LIGHT...

Страница 5: ...could enter panel and an explosive condition could exist Pump cords may be disconnected at pump by removing the cord and cap assembly unplugging sensor wires and removing wire nuts After removal from...

Страница 6: ...O ring seal has been replaced If O ring is nicked or cut replace with new ring This applies to all O rings used in assembly 11 After all leads are reconnected in the connection box make a high voltage...

Страница 7: ...Locktite red on socket head locking screw in end of shaft 12 Before refilling chamber with oil air test as described in replacing stator 13 Refill both chambers with oil as described in replacing stat...

Страница 8: ...art No No Description Qty Ref Part Part No No Description Qty PUMP PUMP V RPM Connection Rotor Stator Connector box Spacer Connector Connector DESCRIPTION PART HP Box B1 Shaft Assy B2 B3 to cord cap B...

Страница 9: ...9 H3HX...

Страница 10: ...perly install operate or maintain the unit in accordance with the printed instructions provided b to failures resulting from abuse accident or negligence c to normal maintenance services and parts use...

Страница 11: ......

Страница 12: ...Line Voltage _________________________________Actual ___________________________________ Voltage to Pumps _____________________________________Actual ___________________________________ Type of Junct...

Отзывы: