4

ENGLISH

APPLICATION

WARNING!

The pump must only be connected to sockets that have been 
installed properly in accordance with the regulations and are 
protected with at least 10 A (slow) and RCD-safety switches 

(30mA).

DANGER!

The pump must never be used when a person is in the water.

Submersible pumps from the U3 and U3 spezial series are suit

-

able for pumping domestic waste water without stones. This 
includes also water from household dishwashers and house-
hold washing machines.

The U3 spezial can also pump aqueous solutions with up to 15% 

salt content and condensate from gas condensing boilers.

NOTICE!

 In outdoor applications, only pumps with at least a 

10-metre mains cable must be used.

When using the pumps, the relevant national laws, regulations 
and stipulations must be adhered to, for example:

Domestic contaminated and waste water

(e.g. EN 12056 in Europe)

Installation of low voltage systems 

(e.g., VDE 0100 in Germany)

For non-standard utilization conditions, further regulations 
must be observed (e.g. VDE 0100 in Germany, part 701: ba-
throoms and shower rooms; part 702: swimming pools and 

fountains and part 737: outdoor use).

Temperatures

The pumped medium must have a temperature of max 35 °C. 
For a short time 60 °C are permissible (S2: 10 min, S3: 30%).
The submersible pump is frost-resistant down to -20 °C when 

stored in dry conditions. When installed, however, it must not 
be allowed to freeze in the water.

Transport

The pump must always be lifted by the handle and never by 
the power supply cable! The pump should only be lowered into 
deeper chambers or pits using a rope or chain.

ELECTRICAL CONNECTION

NOTICE!

  Only  qualified  electricians  may  carry  out  electrical 

works to the pump or the controls.

WARNING!

Before carrying out any works: disconnect the pump and the 
controls from the mains and take steps to ensure that no one 
else can reconnect them to the power supply.
The relevant standards (such as EN standards), country-spe-

cific regulations (such as VDE in Germany), and the regulations 

of the local power supply companies must be observed.

NOTICE! 

Never put the mains plug or a free lead end in water! 

If water gets into the plug, this can cause malfunctions and da-
mage.

Observe the operating voltage (see the type plate)! 
The pump is provided with a winding thermostat. In case of 
unacceptably high temperatures it switches off the pump to 

protect it against possible damage. Unacceptably high tem-
peratures may result e.g. from dry running or mechanical or 
electrical overload. 

CAUTION! 

The pump is switched on again automatically after cooling 
down - risk of injury! 
For this reason, always disconnect the device from the mains 
before remedying the fault! In order to do this, unplug from the 
mains supply or remove the pre-fuses of the pump controls!

INSTALLATION

The pump must be installed as shown in the examples. For in-
stallations in accordance with EN 12056-4, the pressure pipe 

must be laid in a loop above the local backflow level and pro

-

tected with a backflow prevention valve in accordance with EN 

12050-4. 
A correspondingly larger diameter pipe should be used for 
longer pressure pipelines to avoid pipe friction losses. 
With any pump that has no automatic switching, the switch-on 
and switch-off heights can be set variably with a separate level 
control.

 

Our ready to connect level controls can be installed 

without specific electrotechnical skills.

The pump housing is automatically vented via the enclosed 

90° elbow. If this is not desired, the ventilation opening can be 

closed, e.g. for mobile operation.  

Flushing device

The pump can keep the intake section at the bottom of the 
chamber clear of deposits to a large extent if you carry out a 

small modification

: Lever off the foot strainer with a screwdriver, 

unscrew the three red caps and snap the foot strainer back on. 

This reduces the performance of the pump only insignificantly.

 

Low level pumping

Flooded surfaces can be drained down to a residual water level 
of a few mm without using any special accessories. To do so, 
the foot strainer must be levered off with a screwdriver. In the 

case of pumps with an attached control, the float switch must 

be locked in the ON position. It is not possible therefore in low 
level pumping to operate the pump in switching mode.

Содержание U3 K SPEZIAL

Страница 1: ...EN Instruction Manual B 49625 11 2022 01 U3 U3 K U3 K Spezial U3 KS U3 KS Spezial WWW PTS JUNG CO UK...

Страница 2: ...2 Einbaubeispiel Installation example 40 x 40 mm 50 cm Einbaubeispiel Installation example 50 x 50 mm 50 cm Montage GR 32 Installation GR 32...

Страница 3: ...personnel All personnel involved with the operation servicing inspection and installation of the equipment must be suitably qualified for this work and must have studied the instruction manual in dept...

Страница 4: ...ply companies must be observed NOTICE Never put the mains plug or a free lead end in water If water gets into the plug this can cause malfunctions and da mage Observe the operating voltage see the typ...

Страница 5: ...ed at regular intervals according to the hardness of the water Tightening torque MA for A2 screw materials for M 5 MA 5 Nm for Amtec 3 MA 0 7 Nm for Amtec 5 MA 2 Nm QUICK TIPS FOR REMEDYING FAULTS Pum...

Страница 6: ...al 10m kg 3 5 4 4 3 8 DN 32 32 32 mm 10 10 10 S1 35 C S2 60 C 10 min 10 min 10 min S3 60 C 30 30 30 P1 W 320 320 320 P2 W 220 220 220 U V 1 N PE 230 1 N PE 230 1 N PE 230 f Hz 50 50 50 I A 1 4 1 4 1 4...

Страница 7: ...nizzate NL Richtlijnen Geharmoniseerde normen PL Dyrektywy Normy zharmonizowane PT Directiva Normas harmonizadas RO Directiv Norme coroborate SK Smernice Harmonizovan normy SV Direktiv Harmoniserade n...

Страница 8: ...ator Capacitor JP50535 Anschlusseinheit Top cover U3 K 10m JP50541 U3 KS 4m JP50540 U3 KS 10m JP50542 U3 K spezial 10m JP50545 U3 KS spezial 4m JP50543 U3 KS spezial 10m JP50544 Schwimmer Float JP4277...

Страница 9: ...ECHNICAL lf RJUNG SERVICES LIMITED CJPUMPEN Pump Technical Services Limited Pump House Unit 12 Bilton Road Industrial Estate Erith Kent DA8 2AN Tel 01322 357 080 Website www pts jung co uk Email sales...

Отзывы: