INSTALLATION INSTRUCTIONS
57
P
ARAMETER
P07
-
M
INIMUM
BTU
OUTPUT
12.
Enter the parameters menu and select parameter P07. The pressure
gauge will indicate the gas pressure. If this pressure value is different to
that on the rating plate of the boiler (
see paragraph
5.5
‘Gas Data’
)
, use
‘
’ and ‘
’ buttons (D.H.W temperature setting)
to modify the
value of the parameter. The range of settings is 00 - 80.
13.
Press mode selection button ‘
’ to confirm and to render the
new adjustment operative. The parameter number (P07) will appear
on the display.
14.
Press simultaneously ‘
’ and ‘
buttons until
OFF
appears on
the display.
15.
Disconnect the manometer from the pressure test port
‘
B
’ on the gas
valve and carefully tighten the screw making sure there are no gas
leaks.
P07
30
P07
24
Содержание PNCC-32N
Страница 8: ...GENERAL INFORMATION 5 ...
Страница 9: ...GENERAL INFORMATION 6 ...
Страница 10: ...GENERAL INFORMATION 7 ...
Страница 11: ...GENERAL INFORMATION 8 ...
Страница 14: ...INSTALLATION INSTRUCTIONS 11 2 2 Dimensions ...
Страница 15: ...INSTALLATION INSTRUCTIONS 12 2 3 Internal parts of the boiler ...
Страница 16: ...INSTALLATION INSTRUCTIONS 13 2 5 Water circuit ...
Страница 17: ...INSTALLATION INSTRUCTIONS 14 2 5 Circulation pump head flow graph ...
Страница 35: ...INSTALLATION INSTRUCTIONS 32 ...
Страница 41: ...INSTALLATION INSTRUCTIONS 38 36 ...
Страница 43: ...INSTALLATION INSTRUCTIONS 40 ...
Страница 45: ...INSTALLATION INSTRUCTIONS 42 ...
Страница 71: ...MAINTENANCE INSTRUCTIONS 68 6 6 Wiring diagrams DIGITECH TR Printed Circuit Board MIAH403 110 V 60 hz ...
Страница 76: ...MAINTENANCE INSTRUCTIONS 73 6 10 Exploded Drawings ...
Страница 77: ...MAINTENANCE INSTRUCTIONS 74 ...
Страница 78: ...MAINTENANCE INSTRUCTIONS 75 ...
Страница 79: ...MAINTENANCE INSTRUCTIONS 76 ...
Страница 81: ...Pensotti LLC 34 Coffin Ave Brewer ME 04412 P 207 942 3636 F 207 942 3737 www pensottiboiler com ...