background image

Temperature sensors are passive (2-wire) sensors and the

corresponding jumpers must be positioned across both

pins. Humidity transducers are active (3-wire) sensors and

corresponding jumpers must be positioned on one pin (or

removed completely).
Figure 5 shows the jumper positions for the System 450

Reset Control example shown in Figure 3.

Figure 5: Active/Passive sensor jumper positions for

System 450

Note: 

Jumpers are only present in Version 1.

Setting up a control system in the UI

System 450 control modules have a backlit LCD and a

four-button touch pad UI (Figure 4) that enable you to set

up your control system.

1.

Build your control system module assembly and

connect it to power. See 

Setting up a module

assembly

.

Note: 

Every time a module assembly is

powered ON, the control module polls all of

the modules to identify output type (relay

or analog) and assigns a sequential output

number (1 to 9 [0 = 10]) to each output starting

with the control module output on the left. The

output numbers identify each output’s setup

screens in the UI. (See Figure 4.)

2.

Access the System 450 setup screens in the UI. See

Accessing the System 450 Setup screens

.

3.

Set up the control system sensors (inputs) in the UI.

See 

Setting up System 450 Sensors

.

4.

Set up the control system outputs in the UI. See

Setting up System 450 Outputs

.

5.

Set up the clock and occupied/unoccupied schedule

in the UI for systems that use setback. See 

Setting up

time and day of week

 and 

Setting up an occupied/

unoccupied schedule

.

Important:

- When power is disconnected, the time

clock keeps time for 12 hours before

resetting to default; the remaining setup

values entered into the UI remain in non-

volatile memory indefinitely.

- Do not change the module positions

after a System 450 control system is set

up in the UI. System 450 control logic is

set up in the UI according to the Sensor

Types, the output types, and the output

numbers. Changing modules or module

positions in a module assembly that is

already set up in the UI, can change the

output numbers, output types, and the

setup values of the assembly outputs,

which requires setting up the outputs

again.

See Figure 4 for an explanation of the System 450 display

screen and the 4-button touch pad features and functions.

See Table 3 for Reset Control Sensor Types and associated

sensors. See 

Setting up System 450 Sensors

 through

Relay Output and Analog Output that reference the

Reset function

 for System 450 UI setup information and

procedures.

Viewing the Main and System Status
screens

After you install, wire, power on, and set up your control

system in the UI, the Main screens appear on the LCD.

During normal operation, the Main screens automatically

scroll through the current status of each sensor in your

control system, the time and day, and the current Reset

Setpoint value.
The System Status screens display the current status of

each output in your control system and the runtime hours

for each Output Relay. In the Main screen, press 

Next

repeatedly to scroll through and view all of the Main and

System Status screens in your control system.
During normal operation, the Reset Control Main screens

automatically scroll through the current temperature or

humidity sensed at each sensor, the current time and day,

and the current calculated Reset Setpoint (RSP) value. See

the Main Screens row in the setup screens flow chart in

System 450 menu flow example

.

Note:

• You must set up time and day of week for control

applications that use the setback feature, but you

can also set up time and day on control systems

that do not use the setback feature. If the time

and day have not been set up, the Time/Day

Status screen displays 

– –:– –

MON

, and 

AM

.

• Main screens are view-only; selections cannot be

made in Main screens.

During normal operation while the LCD is auto-scrolling

through the Main screens, press 

Next

 repeatedly to

scroll through and view the available System Status

screens. Press and hold 

Up

 and 

Down

 simultaneously

for 5 seconds to access the Setup Start screens and the

System 450 system setup screens.
In the following figure, the screen examples show Sensor

1 sensing 27°F outdoor air at the Master sensor, Sensor

2 sensing 151°F at the boiler water supply outlet, the

System 450 Series Reset Control Modules with Real-Time Clock and Relay Output Installation Guide

6

Содержание System 450 C450RBN-1

Страница 1: ...ith reset control and or real time setback control for temperature and humidity only control applications System 450 expansion modules allow you to control up to 10 outputs which can be relay and anal...

Страница 2: ...lies before mak ing electrical connections More than one disconnec tion or isolation may be required to completely de en ergize equipment Contact with components carrying hazardous voltage can cause e...

Страница 3: ...and input sensor terminals low voltage less than 30V Labels 5V 24V Sn 1 Sn 2 Sn 3 Note Common terminals C are internally connected 2 6 pin module connector 3 Second output relay and terminal block La...

Страница 4: ...ion Module 16 Analog Output 4 Table 1 System 450 terminal wiring information Label Terminal function Wire sizes 24V Accepts 24 VAC supply power when a C450YNN power module is not connected and provide...

Страница 5: ...nd Down for 5 seconds to access the Setup Start screens 7 Menu button Press M to move through the sensor and output setup start screens When moving through the status or setup screens press M to retur...

Страница 6: ...s of the assembly outputs which requires setting up the outputs again See Figure 4 for an explanation of the System 450 display screen and the 4 button touch pad features and functions See Table 3 for...

Страница 7: ...s that the Analog Output is set up with SP EP and OSP OEP and Relay Output 2 has 17 hours of total runtime relay ON Figure 7 System Status screens Accessing the System 450 Setup screens 1 Apply power...

Страница 8: ...screens are view only selections cannot be made in Setup Start screens 2 In the Sn 1 Sensor Type Selection screen press Up or Down to select a Sensor Type F C or Press Next to save your selection and...

Страница 9: ...Setup Start screen Setting up the System 450 Reset Setpoint The System 450 Reset Control Modules feature temperature and humidity setpoint reset capability based on a Master temperature sensor Sn 1 an...

Страница 10: ...screen The remaining figures in this procedure show the setup parameter values selected for the RSP high and low temperature shutdown unoccupied setback and load balancing that are used by the output...

Страница 11: ...en The following figure shows an Shutdown High Temperature value of 65 F selected Figure 20 Shutdown High Temperature Selection screen 7 In the Shutdown Low Temperature Selection screen press Up or Do...

Страница 12: ...e the following sections Setting up a Relay Output with Reset Setpoint Setting up an Analog Output with Reset Setpoint Setting up a Standard Relay Output A standard relay output provides On Off contro...

Страница 13: ...mains off after reaching the OFFT value Minimum Relay OFF Time range is 0 to 300 seconds Press Next to save your selection and go to the next screen The following figure shows 10 seconds selected for...

Страница 14: ...et up in Setting up the System 450 Reset Setpoint Figure 35 Relay Output Setup Start screen 2 In the Sensor Selection screen press Up or Down to select the Reset Setpoint Sensor rES for the output to...

Страница 15: ...nge is 0 to 300 seconds Press Next to save your selection and go to the next screen The following figure shows 0 seconds selected for the minimum OFF Time for Output 2 Figure 40 Minimum Relay OFF Time...

Страница 16: ...gth at End Point OEP The LCD displays different Control Ramp icons for the four control actions The following figure shows an example of the analog output setup values and the resulting output signal...

Страница 17: ...e To set up a Standard Analog Output you must select Sn 1 Sn 2 or Sn 3 in this screen and the selected sensor must already be set up in the System 450 UI See Setting up System 450 Sensors for informat...

Страница 18: ...re limits to set point excursion The following figure shows 0 selected for the Unoccupied Setback value for Output 3 Figure 51 Unoccupied Setback Selection screen 8 In the Integration Constant Selecti...

Страница 19: ...sensor is not selected the remaining output setup screens do not appear If a sensor is already selected for the output the Sensor Selection screen does not appear here the next screen in the setup se...

Страница 20: ...tput When properly set up P I control can drive the load closer to Setpoint than proportional only control Press Next to save your selection and go to the next screen Initially you should select the I...

Страница 21: ...wing figure shows 12 hour clock format selected Figure 67 12 or 24 Hour Clock Selection screen 3 In the Time of Day Setup screen press Up or Down to set the current time Set the clock to real time Pre...

Страница 22: ...e unoccupied times The load balancing feature is not effected in its function as a result of Occupied Unoccupied modes See Figure 3 1 In the Occupied Unoccupied Schedule Setup Start screen press Next...

Страница 23: ...eriods for that day and the entire day is occupied and all outputs operate at their occupied setpoint value Occupied and Unoccupied time periods are available at 15 minute intervals only For example 1...

Страница 24: ...nd menu flow example System screens Description 1 Main screens Note The Main menu screens auto scroll during normal operation After two minutes of inactivity in any screen the display returns to the m...

Страница 25: ...eed 8 Standard analog output setup start screens Mixing valve output 9 Time and day clock setup start screens Note You can set Time and day and occupied or unoccupied schedule for any control system T...

Страница 26: ...VAC AC Full load Amperes 4 9 A AC Locked Rotor Amperes 29 4 A _____________________________________ 10 Amperes AC noninductive at 24 240 VAC Pilot Duty 125 VA at 24 240 VAC Clock accuracy 4 minutes pe...

Страница 27: ...or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different fro...

Страница 28: ...2020 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www penncontrols com...

Отзывы: