Table 1: System 450 terminal wiring information

Label

Terminal function

Wire sizes

LNC1, LNC2

1

Connects equipment control circuit to the normally closed contact on the SPDT

1

 relay.

LNO1, LNO2

Connects equipment control circuit to the normally open contact on the SPDT

1

 relay.

LC1, LC2

Connects line (power) to common on the SPDT

1

 relay.

0.08 mm

2

 to 2.5 mm

2

28 AWG to 14 AWG

1

See Internal SPDT Relay insert in Figure 2 for more System 450 relay contact and terminal information. See 

System 450 Series Reset

Control Modules with Real-Time Clock and Relay Output technical specifications

 for SPDT relay electrical ratings.

Figure 4: System 450 Reset Control Module output

relay LEDs, LCD, and four-button touch pad UI

Table 2: System 450 Control Module Output Analog

LEDs, LCD, four-button touchpad UI

Callout

Feature

Description

1

Status or setup
value

Displays the current input status, output status, or
setup parameter value for the displayed input sensor
or output. Press 

Down

 or 

Up

 to select a different

parameter value when the value is flashing. Here,
100 = 100%.

2

LED

Green LEDs on Control Modules and Expansion
Modules with relays (only) indicate if the associated
Relay Output is On or Off.

3

Output (or
Sensor) number

Displays a numerical value that identifies the output
or sensor associated with the status or setup
value shown on the screen. Output numbers are
automatically determined by the outputs' physical
positions (left to right) in the module assembly. Here,
4 = Output 4.

4

Control ramp
icon

Displays whether an analog output increases
or decreases as the sensor input increases, and
whether the output signal strength is at minimum or
maximum when the sensed property is at Setpoint.
The control ramp icon displayed is determined by the
output's SP, EP, Pb, OSET, OSP, and OEP setup values.

5

Next button

In the Main screens, press 

Next

 to scroll through the

system status screens. In a setup screen, press 

Next

to save the flashing setup value and go to the next
setup screen.

6

Up and Down
buttons

Press 

Up

 or 

Down

 to select a different value for any

flashing value in the setup value field. In the Main
sensor status screens, press and hold both 

Up

 and

Down

 for 5 seconds to access the Setup Start screens.

7

Menu button

Press 

M

 to move through the sensor and output

setup start screens. When moving through the status
or setup screens, press 

M

 to return to the status start

screen or setup start screen.

Table 2: System 450 Control Module Output Analog

LEDs, LCD, four-button touchpad UI

Callout

Feature

Description

8

Status or setup
identifier

Displays the unit of measurement, output, sensor
number, or setup parameter for the displayed
status or setup value. Here, the setup identifier OSP
represents % output signal strength at setpoint.

9

LCD

Backlit LCD screen. The LCD brightness is adjustable.
During normal operation, the LCD displays the Main
screens.

Setup and adjustments

A System 450 reset control system consists of one reset

control module, one to three input sensors, and one to

ten outputs that provide any combination of (On/Off)

relay control or (0–10 VDC or 4–20 mA) analog control.

Figure 3 shows a reset control system for two boilers, a

boiler water circulation pump, and an outside air damper.

Setting up a module assembly

1.

Determine the controlled conditions, sensor types,

and value ranges required for your control system,

and select the appropriate System 450 sensors.

2.

Determine the number and type (relay or analog)

of outputs required to control your application, and

select the appropriate System 450 control module

and expansion modules.

3.

Assemble the control and expansion modules,

starting with the control module on the left.

Note: 

If you use a C450YNN-1 power module, it

must be plugged into the control module. Plug

in any expansion modules (for your control

system) to the right of the power module.

4.

Apply supply power to the module assembly.

You can now set up your control system in the System 450

reset control module UI.

Note: 

After you power on your module assembly,

you can set up your control system in the control

module UI before wiring the sensors or outputs to

your assembly.

Setting active/passive sensor jumpers

Before putting your System 450 reset control system into

operation, you must set up each sensor in your system

as either passive or active by positioning the jumper on

the terminal pins on the terminal block located below the

sensor terminal block. See Figure 3.

System 450 Series Reset Control Modules with Real-Time Clock and Relay Output Installation Guide

5

Содержание System 450 C450RBN-1

Страница 1: ...ith reset control and or real time setback control for temperature and humidity only control applications System 450 expansion modules allow you to control up to 10 outputs which can be relay and anal...

Страница 2: ...lies before mak ing electrical connections More than one disconnec tion or isolation may be required to completely de en ergize equipment Contact with components carrying hazardous voltage can cause e...

Страница 3: ...and input sensor terminals low voltage less than 30V Labels 5V 24V Sn 1 Sn 2 Sn 3 Note Common terminals C are internally connected 2 6 pin module connector 3 Second output relay and terminal block La...

Страница 4: ...ion Module 16 Analog Output 4 Table 1 System 450 terminal wiring information Label Terminal function Wire sizes 24V Accepts 24 VAC supply power when a C450YNN power module is not connected and provide...

Страница 5: ...nd Down for 5 seconds to access the Setup Start screens 7 Menu button Press M to move through the sensor and output setup start screens When moving through the status or setup screens press M to retur...

Страница 6: ...s of the assembly outputs which requires setting up the outputs again See Figure 4 for an explanation of the System 450 display screen and the 4 button touch pad features and functions See Table 3 for...

Страница 7: ...s that the Analog Output is set up with SP EP and OSP OEP and Relay Output 2 has 17 hours of total runtime relay ON Figure 7 System Status screens Accessing the System 450 Setup screens 1 Apply power...

Страница 8: ...screens are view only selections cannot be made in Setup Start screens 2 In the Sn 1 Sensor Type Selection screen press Up or Down to select a Sensor Type F C or Press Next to save your selection and...

Страница 9: ...Setup Start screen Setting up the System 450 Reset Setpoint The System 450 Reset Control Modules feature temperature and humidity setpoint reset capability based on a Master temperature sensor Sn 1 an...

Страница 10: ...screen The remaining figures in this procedure show the setup parameter values selected for the RSP high and low temperature shutdown unoccupied setback and load balancing that are used by the output...

Страница 11: ...en The following figure shows an Shutdown High Temperature value of 65 F selected Figure 20 Shutdown High Temperature Selection screen 7 In the Shutdown Low Temperature Selection screen press Up or Do...

Страница 12: ...e the following sections Setting up a Relay Output with Reset Setpoint Setting up an Analog Output with Reset Setpoint Setting up a Standard Relay Output A standard relay output provides On Off contro...

Страница 13: ...mains off after reaching the OFFT value Minimum Relay OFF Time range is 0 to 300 seconds Press Next to save your selection and go to the next screen The following figure shows 10 seconds selected for...

Страница 14: ...et up in Setting up the System 450 Reset Setpoint Figure 35 Relay Output Setup Start screen 2 In the Sensor Selection screen press Up or Down to select the Reset Setpoint Sensor rES for the output to...

Страница 15: ...nge is 0 to 300 seconds Press Next to save your selection and go to the next screen The following figure shows 0 seconds selected for the minimum OFF Time for Output 2 Figure 40 Minimum Relay OFF Time...

Страница 16: ...gth at End Point OEP The LCD displays different Control Ramp icons for the four control actions The following figure shows an example of the analog output setup values and the resulting output signal...

Страница 17: ...e To set up a Standard Analog Output you must select Sn 1 Sn 2 or Sn 3 in this screen and the selected sensor must already be set up in the System 450 UI See Setting up System 450 Sensors for informat...

Страница 18: ...re limits to set point excursion The following figure shows 0 selected for the Unoccupied Setback value for Output 3 Figure 51 Unoccupied Setback Selection screen 8 In the Integration Constant Selecti...

Страница 19: ...sensor is not selected the remaining output setup screens do not appear If a sensor is already selected for the output the Sensor Selection screen does not appear here the next screen in the setup se...

Страница 20: ...tput When properly set up P I control can drive the load closer to Setpoint than proportional only control Press Next to save your selection and go to the next screen Initially you should select the I...

Страница 21: ...wing figure shows 12 hour clock format selected Figure 67 12 or 24 Hour Clock Selection screen 3 In the Time of Day Setup screen press Up or Down to set the current time Set the clock to real time Pre...

Страница 22: ...e unoccupied times The load balancing feature is not effected in its function as a result of Occupied Unoccupied modes See Figure 3 1 In the Occupied Unoccupied Schedule Setup Start screen press Next...

Страница 23: ...eriods for that day and the entire day is occupied and all outputs operate at their occupied setpoint value Occupied and Unoccupied time periods are available at 15 minute intervals only For example 1...

Страница 24: ...nd menu flow example System screens Description 1 Main screens Note The Main menu screens auto scroll during normal operation After two minutes of inactivity in any screen the display returns to the m...

Страница 25: ...eed 8 Standard analog output setup start screens Mixing valve output 9 Time and day clock setup start screens Note You can set Time and day and occupied or unoccupied schedule for any control system T...

Страница 26: ...VAC AC Full load Amperes 4 9 A AC Locked Rotor Amperes 29 4 A _____________________________________ 10 Amperes AC noninductive at 24 240 VAC Pilot Duty 125 VA at 24 240 VAC Clock accuracy 4 minutes pe...

Страница 27: ...or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different fro...

Страница 28: ...2020 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www penncontrols com...

Отзывы: