P545 Series Electronic Lube Oil Control Product/Technical Bulletin    

5

 

Mounting 

Mount the P545 Control 

Use the mounting holes shown in Figure 5 for 

mounting the control on a flat vertical surface. Two 

No. 10 screws are provided for this purpose. Do not 

use longer screws, as damage to internal components 

may occur. Mount the control in an upright position, 

and avoid warping or bending the case. 
Use the Universal Mount (Part No. 271-51) to mount 

the control to a vertical or horizontal surface. This 

requires two 10-32 UNF-2B screws (not included). 

Mounting Holes for a

Flat Vertical Surface

No. 10 Screws 

(2 provided)

Universal Mounting 

Bracket (UMB)

10-32 UNF-2B Screw

(not provided)

12

01

10

12

_5

.c

dr

Mounting Holes 

for UMB

 

Figure 5: Mounting the P545 Control 

Mount the P400 Switch 

If you modify an existing refrigeration compressor to 

accept the P400 switch, it may involve installing a 

sensor block (such as a Johnson Controls® 

CST29A-600C) or other part. For proper installation, 

follow all procedures recommended by the compressor 

manufacturer. 
To mount the P400 switch: 
1.  Wet the switch nozzle and gasket with oil. 
2.  Fit the gasket over the nozzle as shown in 

Figure 6. 

3.  Install the switch in the lube oil port according to 

the compressor manufacturer’s instructions. 

4.  Hand-tighten the switch until the surfaces of 

gasket and compressor housing meet. 

5.  Use a torque wrench to tighten the sensor until 

sealed (40 lb

ft recommended torque). 

Wiring 

See Figure 7 through Figure 12 for typical wiring 

diagrams, or refer to the compressor manufacturer’s 

specifications. Make all wiring connections using 

copper conductors only. Ensure all wiring conforms to 

the National Electrical Code and local regulations. 

!

  WARNING:  Risk of Electric Shock. 

Disconnect the power supply before making electrical 

connections. Contact with components carrying 

hazardous voltage can cause electric shock and may 

result in severe personal injury or death. 

AVERTISSEMENT:  Risque de décharge 

électrique.

 Débrancher l'alimentation avant de réaliser 

tout branchement électrique. Tout contact avec des 

composants conducteurs de tensions dangereuses 

risque d'entraîner une décharge électrique et de 

provoquer des blessures graves, voire mortelles. 

Wire the P400 Switch 

Use this procedure to connect the P400 switch to the 

control: 
1.  Insert the plug into the connector until it snaps and 

locks in place. See Figure 6. 

2.  Connect the wiring harness to the P545 control at 

P2. See Figure 13 for the location and orientation 

of the differential oil pressure switch connection. 

Note: 

The control does not function properly if the 

wiring harness is connected improperly at the circuit 

board. 

12

01

10

12

_6

.c

dr

 Lube Oil Switch

Wiring

Harness

To P2 Connector

Insert

Plug

Switch

Nozzle

Gasket

 

Figure 6: Connecting the Wiring Harness to the 

P400 Switch 

Содержание P545 Series

Страница 1: ...P545 Electronic Lube Oil Control with P400 Single Point Oil Pressure Differential Switch Features and Benefits Single Pole Double Throw SPDT Relay Contacts for Liquid Line Solenoid and Alarm Applicati...

Страница 2: ...ow LED On Compressor contacts close LLS contacts remain closed and alarm remains open green LED On yellow LED On Is the net lube oil pressure sufficient Timer counts down yellow LED Off Green and yell...

Страница 3: ...oil pressure is below opening point If the oil pressure is above opening point more than it is below opening point the control does not shut down the compressor If the oil pressure drops continuously...

Страница 4: ...the P545 control and the P400 switch 2 When the P445 control is wired to a P400 switch The Test button may operate when first powered up however after a couple minutes of operation the Test Switch fun...

Страница 5: ...surfaces of gasket and compressor housing meet 5 Use a torque wrench to tighten the sensor until sealed 40 lb ft recommended torque Wiring See Figure 7 through Figure 12 for typical wiring diagrams o...

Страница 6: ...r Diagrams for the P545 Control M1 M2 L2 120 240 P545 NCA NOA CMA L1 L2 L3 Compressor Contactor Wire Jumper Low Pressure Control High Pressure Control Alarm Connection 12011012_8 cdr Figure 8 Typical...

Страница 7: ...L3 Compressor Contactor Optional Alarm Connection Low Pressure Control High Pressure Control W1 W2 Remove resistor R39 when using the R310AD switch R39 Power for Alarm Circuit R310AD Switch 12011012_...

Страница 8: ...mpressor contactor is energized but the lube oil pressure is below the opening point Timing circuit is active Yellow TIMING LED only Power to the control has been interrupted and restored before the a...

Страница 9: ...e supply voltage Reconnect the compressor leads to the contactor or reset the disconnect If an R310AD switch is used reconnect the compressor leads to the contactor See Figure 13 6 Re energize the sup...

Страница 10: ...the P400 switch 2 Use a single piece of 22 gauge wire as a jumper between the common and signal terminals of the wiring harness 3 Press RESET 4 If the green LED lights and the yellow LED turns off rep...

Страница 11: ...k compressor for internal overloads 2 Check the compressor wiring 3 Check compressor s contactor 4 Check compressor for general failure Ordering Information Use the following tables to order the P545...

Страница 12: ...3 ft 1 m length wiring harness WHA P400 125C 4 ft 1 1 4 m length wiring harness WHA P400 250C 8 ft 2 1 2 m length wiring harness WHA P400 430C 14 ft 4 1 3 m length wiring harness R310AD 1C Low Voltage...

Страница 13: ...240 VAC Backplate Material Case and Cover Material Cold rolled steel High impact thermoplastic Ambient Operating Conditions 40 to 131 F 40 to 55 C Ambient Storage Conditions 40 to 185 F 40 to 85 C App...