    P545 Series Electronic Lube Oil Control Product/Technical Bulletin 

Operation 

Figure 2 shows an operational flowchart for the P545 control. 

Power to the refrigeration control

system is interrupted and the 

anti-short cycling timer starts.

Operating control energizes the P545 control,

and if time other than zero is selected, the

anti-short cycle timer continues to time out.  

Has anti-short

cycle delay 

time elapsed?

No

No

No

No

Yes

Yes

Yes

Yes

Do you want

short cycle

to continue?

Yellow LED On

Compressor contacts close;

LLS contacts remain closed 

and alarm remains open;

green LED On;

yellow LED On.

Is the net

lube oil pressure

sufficient?

Timer 

counts down;

yellow 

LED Off.

Green and yellow LEDs On

time delay counts up.

Has lube

delay timeout

limit been

reached?

Alarm contacts close;

compressor contacts and 

liquid line solenoid contacts open;

red LED On, yellow and green LEDs Off.

Correct

lubrication problem

and press the 

Reset button.

Red LED Off;

alarms clear.

Low lube oil pressure 

time delay initiated.

Compressor  Contacts:  M1 to M2

Alarm Contacts:  CMA to NOA
 
Liquid Line Solenoid Contacts:  CMA to NCA

Note:

.

Push Reset button.

;

12

01

10

2_

2.

cd

r

 

Figure 2: P545 Control Flowchart 

Содержание P545 Series

Страница 1: ...P545 Electronic Lube Oil Control with P400 Single Point Oil Pressure Differential Switch Features and Benefits Single Pole Double Throw SPDT Relay Contacts for Liquid Line Solenoid and Alarm Applicati...

Страница 2: ...ow LED On Compressor contacts close LLS contacts remain closed and alarm remains open green LED On yellow LED On Is the net lube oil pressure sufficient Timer counts down yellow LED Off Green and yell...

Страница 3: ...oil pressure is below opening point If the oil pressure is above opening point more than it is below opening point the control does not shut down the compressor If the oil pressure drops continuously...

Страница 4: ...the P545 control and the P400 switch 2 When the P445 control is wired to a P400 switch The Test button may operate when first powered up however after a couple minutes of operation the Test Switch fun...

Страница 5: ...surfaces of gasket and compressor housing meet 5 Use a torque wrench to tighten the sensor until sealed 40 lb ft recommended torque Wiring See Figure 7 through Figure 12 for typical wiring diagrams o...

Страница 6: ...r Diagrams for the P545 Control M1 M2 L2 120 240 P545 NCA NOA CMA L1 L2 L3 Compressor Contactor Wire Jumper Low Pressure Control High Pressure Control Alarm Connection 12011012_8 cdr Figure 8 Typical...

Страница 7: ...L3 Compressor Contactor Optional Alarm Connection Low Pressure Control High Pressure Control W1 W2 Remove resistor R39 when using the R310AD switch R39 Power for Alarm Circuit R310AD Switch 12011012_...

Страница 8: ...mpressor contactor is energized but the lube oil pressure is below the opening point Timing circuit is active Yellow TIMING LED only Power to the control has been interrupted and restored before the a...

Страница 9: ...e supply voltage Reconnect the compressor leads to the contactor or reset the disconnect If an R310AD switch is used reconnect the compressor leads to the contactor See Figure 13 6 Re energize the sup...

Страница 10: ...the P400 switch 2 Use a single piece of 22 gauge wire as a jumper between the common and signal terminals of the wiring harness 3 Press RESET 4 If the green LED lights and the yellow LED turns off rep...

Страница 11: ...k compressor for internal overloads 2 Check the compressor wiring 3 Check compressor s contactor 4 Check compressor for general failure Ordering Information Use the following tables to order the P545...

Страница 12: ...3 ft 1 m length wiring harness WHA P400 125C 4 ft 1 1 4 m length wiring harness WHA P400 250C 8 ft 2 1 2 m length wiring harness WHA P400 430C 14 ft 4 1 3 m length wiring harness R310AD 1C Low Voltage...

Страница 13: ...240 VAC Backplate Material Case and Cover Material Cold rolled steel High impact thermoplastic Ambient Operating Conditions 40 to 131 F 40 to 55 C Ambient Storage Conditions 40 to 185 F 40 to 85 C App...

Отзывы: