A11 conformity declaration
Table 8: Conformity declaration
Information
Description
Purpose of the
control
Low temperature cutout control
Construction of
the control
Electromechanical independently
mounted control
Number of cycles 30K cycles auto reset, 6K cycles
manual reset
Method of
mounting the
control
Permanently attached through hole
in mounting bracket
Method of
earthing the
control
Wiring binding screw terminal
Type 1 or Type 2
action
Type 1.B; micro-disconnection
External pollution
situation
Pollution degree 3
Internal pollution
situation
Pollution degree 2
Rated impulse
voltage
4,000 VAC
Ball pressure
temperature
Switch component 302°F (150°C)
Field wiring
rating
Use copper conductors only, rated at
least 194°F (90°C)
Switch
SPST (A11A, A11B), SPDT (A11D,
A11E)
Enclosure
UL: Type 1 (NEMA)
Wiring
connection
Three color-coded screw terminals,
SPDT only, and one ground terminal
Conduit
connection
One 7/8 in. (22 mm) hole for 1/2
in. (12.7 mm) trade size (or PG16)
conduit
Ambient
conditions
0°F (-18°C) to 140°F (60°C)
Compliance
North
America
cULus listed; UL60730,
CSA E60730 File SA516
Product warranty
This product is covered by a limited warranty, details
Software terms
Use of the software that is in (or constitutes)
this product, or access to the cloud, or hosted
services applicable to this product, if any, is
subject to applicable end-user license, open-source
software information, and other terms set forth at
www.johnsoncontrols.com/techterms
Your use of this
product constitutes an agreement to such terms.
Single point of contact
APAC
Europe
NA/SA
JOHNSON CONTROLS
C/O CONTROLS PRODUCT
MANAGEMENT
NO. 32 CHANGJIJANG RD NEW
DISTRICT
WUXI JIANGSU PROVINCE 214028
CHINA
JOHNSON CONTROLS
WESTENDHOF 3
45143 ESSEN
GERMANY
JOHNSON CONTROLS
507 E MICHIGAN ST
MILWAUKEE WI 53202
USA
Contact information
Contact your local branch office:
www.johnsoncontrols.com/locations
Contact Johnson Controls:
A11 Series Low Temperature Cutout Control Installation Guide
7