background image

 CAUTION

Risk of Environmental and Property Damage

Coil and secure excess capillary tubing away from

contact with sharp or abrasive objects or surfaces.

Vibration and sharp or abrasive objects in contact

with capillary tubes can cause damage that may

result in release of the chemical charge in the

sensing element, which may result in damage to the

environment or property.

 CAUTION

Risk of Property Damage

Do not dent or deform the sensing bulb. Dents or

deformations in the sensing bulb can change the

calibration, may cause the control to operate at

temperatures other than the setpoint, and may result

in other property damage.

Important:

• When you drill holes or drive screws to mount the

sensing elements, be careful not to puncture or

damage hydronic coils.

• Use only the mounting screws supplied with the

Universal Mounting Bracket to avoid damage to

the internal components. Be careful not to distort

or bend the control case when you mount the

control to an uneven surface. The use of other

screws or bending the control case voids the

warranty.

• Locate the control case and bellows where the

ambient temperature is always warmer than

the setpoint. The control operates only from

the lowest temperature along any 14 in. to 16

in. (356 mm to 406 mm) length of the sensing

element.

• Locate low temperature cutout controls in areas

protected from the effects of weather. If you

mount the control in an area that is exposed to

the weather or other wet environments, equip it

with an outdoor enclosure.

• It is important to mount the low temperature

cutout control in the correct location. Expose the

capillary to all areas on the coil where a risk of low

temperatures is present.

Observe the following guidelines when you mount A11

Series low temperature cutout controls.
• Mount the control upright in an accessible location,

where the control body, capillary tube, and sensing

bulb are not subject to damage, and the control is in

the highest possible position of the entire installation.

• Mount the control upstream from mixed air or chilled

water coils.

• Mount the control downstream from preheat coils.

• Mount the control upright on flat, vertical, or horizontal

surfaces using accessory brackets. These controls have

NEMA 1 enclosures.

• Mount the capillary in a serpentine fashion so that it

slopes gently downhill at an angle not greater than 5°.

Do not permit any dips, bends, or kinks in the capillary,

and install the last segment within 6 in. (152.4 mm) of

the bottom of the coil.

Figure 4: Control capillary orientation

Table 3: Control capillary orientation

Callout

Description

A

Correct. Orient the capilliary horizontally.

B

Incorrect. Do not orient the capilliary

vertically.

Mounting in an accessible location

Before you begin:  

Sometimes, the coil face offers nothing that can hold

the tie-wrapped sensing element. In these cases, use

1/2 in. (13 mm) EMT, hard copper tubing, or Unistrut to

build supports to fasten the sensing element. Fasten the

sensing element to fixed supports to hold the element

in place and prevent movement in the air stream. Field-

fabricated supports often take the form of a rack with

vertical supports. To determine the proper location, see

Figure 1.

1. Determine the best mounting location for the low

temperature cutout control. Locate the control

as high as possible on the side of the duct or on

a nearby wall, panel, or structural support. The

optimum mounting position is with the element

bellows pointing down.

2. When you mount the control directly to a flat

vertical surface, insert two screws or bolts through

the two outer holes on the back of the control case.

3. When you mount the control to a flat horizontal

surface, use the two inner holes with the mounting

bracket and the supplied screws.

4. Build and install any field-fabricated supports that

are necessary to hold the sensing element in place.

5. Use the control’s mounting bracket as a template

to mark the location for the mounting screws.

6. Drill an 5/16 in. (8 mm) entry hole for the sensing

element.

7. Feed the entire length of the sensing element

through the entry hole.

A11 Series Low Temperature Cutout Control Installation Guide

3

Содержание A11 Series

Страница 1: ...tream side of the coil Expose the element to all areas where low temperatures may occur 2 Horizontally serpentine the 20 ft 6 1 m long sensing element across the face of the coil to sense temperatures...

Страница 2: ...u mount the control below the sensing element prevent possible nuisance alarms by mounting the control in a conditioned space When using the A11 Series control coil the excess capillary inside the con...

Страница 3: ...f the entire installation Mount the control upstream from mixed air or chilled water coils Mount the control downstream from preheat coils Mount the control upright on flat vertical or horizontal surf...

Страница 4: ...ly sleeve around the capillary at the point where it passes through the entry hole in the duct work Slit the tubing lengthwise to permit easy installation You do not normally need caulking or sealant...

Страница 5: ...that you can position the capillary whip close to the support See Figure 6 11 Place a 4 in 10 1 cm box cover with the center knockout removed over the upper end of the support assembly and use a lock...

Страница 6: ...lb senses a temperature equal to or lower than the setpoint the contacts open on SPST controls or the circuit between the Red and Yellow terminals open on SPDT controls The A11A and A11D models lock o...

Страница 7: ...1 2 in 12 7 mm trade size or PG16 conduit Ambient conditions 0 F 18 C to 140 F 60 C Compliance North America cULus listed UL60730 CSA E60730 File SA516 Product warranty This product is covered by a l...

Страница 8: ...2021 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www penncontrols com...

Отзывы: