The MLS Gateway forms the interface between the PHC system and the
ExOr MLS-system.
Version 3.0 of the PHC software provides 16 PHC control channels for the
MLS Gateway. These can be used to actuate 16 MLS zones. One control
channel can actuate one MLS zone each (max 100).
1
ON
2
6 7 8
3 4 5
D+ D–
Module Bus
MLS-Gateway
940/16 MLS-G
Status
MLS
PHC
coding switch
module adres
status Led
bus connection Phc-bus
modular sockets 6-pin
MLs-bus-connection
Screw terminals D+, D-
status Led
green
PHC active, module ready
red
Boot loader active
flashing red
MLS Gateway incorrectly or incompletely initialised
off
No operating voltage, other error
notes:
– Detailed expert knowledge for programming a PHC system and
MLS systems are required.
– Before the module can be used in the PHC system
and the PHC functions programmed, Version 3.0 of the PHC soft
ware must first be installed! (See PHC manual.)
– This requires the PHC control module Version 3.0 or later!
– Read through the operating instructions carefully before putting
the device into service.
sAfety
This device is only intended to be used for its stated application. Unautho-
rised conversions, modifications or changes are not permissible! This de
-
vice may not be used in conjunction with other devices whose operation
could present a hazard to persons, animals or property.
the following must be observed:
• Prevailing statutes, standards and regulations.
• State-of-the-art technology at the time of installation.
• The device’s operating instructions.
• Operating instructions can only cite general stipulations.
These are to be viewed in the context of a specific system.
the following systems may not be switched:
• Safety switches such as EMERGENCY OFF
•
Emergency power supplies
•
Fire alarm systems
•
Emergency lighting systems
technicAL inforMAtion
own consumption
Less than 0,25W
Power supply Phc
system (Phc bus)
Nom. 24 V DC (SELV)
21-28 V DC (ripple voltage 5 %)
current consumption
(Phc system)
max. 10 mA for the PHC power supply
control channel 0-15
(Phc system)
Control of max. 16 MLS-zones
(1 zone per PHC control channel)
coding
DIP switch, 8-pin
Ambient temperature
+10 to +50 °C
storage temperature
-20 to +60 °C
connections
2 modular sockets 6-pin (PHC bus)
2 screw terminals per control channel (D-, D+)
screw terminals
max. 2 x 1,5 mm²
test specifications
EN 50090
Approbationen
CE
Protection level
IP20
dimensions
Width = 38 mm (2TE)
Height = 55 mm
instALLAtion
important installation information !
The installation, commissioning and programming (PHC software)
may be carried out by authorised electricians only. The applicable
laws and standards of the country in which the device is operated
must be complied with. The MLS gateway is designed for mounting
on a 35mm top hat rail acc. EN 50022 in in-/on-wall distribution
housing with screwed cover.
– The devices can be mounted directly next to each other.
–
Attention!
Do not apply any grid voltage (230/240V~) to the control
channels. Connection can damage the module or PHC system!
– Switch off power supply before connecting or disconnecting bus line.
– Before setting the module address, the PHC module needs to be
switched off and it must be secured against electrical discharge.
– Do not set the same module addresses for MLS Gateways!
coding sWitch
The coding switch sets the module address. The set-
ting is presented in the PHC software under menu
item „
Components
Modules
“.
notes:
– Do not set the same module addresses for MLS Gateways.
– Before setting the module address, the PHC module needs to be
switched off and it must be secured against electrical discharge.
bus connection (dAtA connection)
Establishing the data connection between MLS Gateway and neighbouring
module or module in the next distributor row. The connection is establis-
hed via the modular sockets of the modules through the PHC bus line. The
modular sockets are switched parallel (except in the PHC power supply)
and therefore freely selectable as input or control output. The MLS bus
is usually connected with an unshielded twisted pair line (2 x 1.5 mm²).
bus connection Phc-bus
1
ON
2
6 7 8
3 4 5
D+ D–
Module Bus
MLS-Gateway
940/16 MLS-G
Status
MLS
PHC
MLs-bus-connection
1
ON
2
6 7 8
3 4 5
D+ D–
Module Bus
MLS-Gateway
940/16 MLS-G
Status
MLS
PHC
notes:
– Switch off power supply before connecting or disconnecting bus line.
– The PHC module can be positioned anywhere in the data line.
– A PHC bus line of 30 cm length is included.
coMMissioning
• Carry out installation and switch on electrical system.
•
Carry out PHC programming with PHC software V3.0.
• Carry out program transfer with PHC software V3.0.