GENERATOR OVERVOLTAGE PROTECTION
➢
Protection Reference: 25% of the reference voltage set by the trimpot
Vad
.
➢
Time for protection action: 1 second.
➢
Signaling: Alarm Led constantly lit in
Strong Blue
.
EXCITATION OVERCURRENT PROTECTION
➢
Protection Reference:
12,5 A.
➢
Time for protection action:
1 second.
➢
Signaling
:
Alarm Led constantly lit in
Red
.
ARMATURE OVERCURRENT PROTECTION
➢
Protection Reference: 15% above rated CT current.
➢
Time for protection action: 2 seconds.
➢
Signaling: Alarm Led constantly lit in
Yellow
.
ROTATING DIODE FAULT
The regulator is constantly measuring the fluctuations that occur in the excitation current, when a
variation occurs above a percentage of the average current, and the actuation time exceeds a
defined time the regulator signals an alarm of the occurrence of the fault.
➢
Percentage reference of the average excitation current: 30%.
➢
Time for protection action: 5 seconds.
➢
Signaling: Alarm Led constantly lit in
Cyan
(
Blue-green
).
Figure 8
–
Operation of protections