Peco Perfomance PRO T4500 Скачать руководство пользователя страница 4

© COPYRIGHT 2010 PECO, INC.  ALL RIGHTS RESERVED.   

 

 

 

P/N 70476 3220-2265 REV 00

4

Part vII: PerForm aDvanceD conFIGUratIon

Perform advanced confi guration before attaching the thermostat to the wallplate. 

Advanced confi guration is done by simultaneously pressing the lower left and lower right 

keys for about fi ve seconds (see Fig. 7), which gives the user access to Service Menus. 

Use Table 2 of this Installation Guide to set each desired Service Menu item. Advanced 

confi guration allows the user to confi gure the thermostat to match the system type and to 

customize several thermostat settings.

It is also recommended to review the T4000 Series Operating Manual to learn how to 

program basic settings, such as setting the temperature display mode and other useful 

functions. 

Part vIII: moUnt the t4500 onto the wallPlate

1.  Position the thermostat slightly above the mounted wallplate (see Fig. 8), then secure 

the hooks on the back side of the thermostat to the hinge pockets on the wallplate. 

note: the top back side of the thermostat should slip into the hinge pockets 

easily. Do not use excessive force. 

2.  Align the pins on the back side of the thermostat with the terminal blocks on the 

wallplate. 

3.  Gently bring down the thermostat onto the wallplate so the pins on the back of the 

thermostat fi t into the terminal blocks on the wallplate. 

4.  Attach the retaining screw to the underside of the thermostat as shown (see Fig. 9). 

Part IX: verIFY thermostat oPeratIon wIth sYstem tests

System test verifi cation is highly recommended to verify thermostat operation. Follow at 

least one procedure in the system tests below. Refer to the Service Menus (see Table 2) 

for more tests. For all tests, press 

next

 to continue to the following system test, which is 

the next available Service Menu. Press 

Done

 only if fi nished performing all system tests. 

Pressing 

Done

 exits the Service Menus and turns off all active outputs. 

sYstem test maIn oUtPUt (heat) 

1.  On the thermostat, press the lower left and lower right keys simultaneously for about 

fi ve seconds. 

Next

,

 

Go Back

, and 

Done

 appear (see Fig. 10).

2.  Press 

Next 

until Service Menu 610 appears in the display. 

(Default value “00” appears below Service Menu.) 

3.  In Service Menu 610, press ▲/ ▼to select option “01,” Heat Stage 1 (see Fig.11).

note

: If 01 is selected, the thermostat will activate the associated output for 10 minutes. 

The user should observe that the fan output (with heat) turns on. The user may also 

test more stages of heat according to what is available for the system type. 

4.  Press 

Done

 to complete the system test and exit the Service Menus. After verifying 

the system test, the outputs are disabled and the fan will stop. 

Figure 8. 

Secure the hooks 

on the back side of 

the thermostat to the 

wallplate.

Retaining screw

Figure 9. 

Mount the thermostat 

onto the wallplate. 

Figure 7. 

Access Service Menus 

by pressing the lower 

right and lower left 

keys simultaneously. 

Figure 11.  

Press Done 

to complete 

testing and 

exit Service 

Menus, 

or Next to 

continue 

tests. 

Figure 10.

Service Menu 610 

allows the user to 

perform System 

Test (Heat).

Service Menu

Default value 

(appears 

automatically)

Содержание Perfomance PRO T4500

Страница 1: ...nd heat pump applications System mode selections Off Heat Cool Auto Stages 1 Heat 1 Cool 2 Heat 1 Cool 1 Heat 2 Cool 2 Heat 2 Cool 3 Heat 2 Cool Fan control Cycling Auto or Continuous On 1 Speed Permanent memory All device settings are stored in permanent memory Connections for Remote Sensors indoor and occupancy caUtIon 24 vac low voltage thermostat Do not install on voltages higher than 30 vac U...

Страница 2: ... side 24 VAC sc Sensor Common sc Sensor Common s1 Indoor Remote Sensor s1 Indoor Remote Sensor System Type 1 1H 1C Conventional System Type 2 1H 1C Heat Pump TERM Function TERM Function C Common C Common W1 Heat B O Reversing Valve W2 AUX G Fan G Fan A A E E Y1 Cool Y1 Compressor Y2 Y2 RH Power for Heating RH Power for Heating RC Power for Cooling RC Power for Cooling System Type 3 Heat only witho...

Страница 3: ...allplate Assure that the metal jumper connects RC and RH Connect power side to the RC RH and assure that the jumper remains in place two transformer system The T4000 T4500 is shipped with a jumper connecting terminals RH and RC If the heating and cooling equipment do not use separate transformers leave this jumper in place If separate transformers are required remove this jumper With the jumper re...

Страница 4: ...wIth sYstem tests System test verification is highly recommended to verify thermostat operation Follow at least one procedure in the system tests below Refer to the Service Menus see Table 2 for more tests For all tests press next to continue to the following system test which is the next available Service Menu Press Done only if finished performing all system tests Pressing Done exits the Service...

Страница 5: ...ostat press the lower left and lower right keys simultaneously for about five seconds Next Go Back and Done appear see Fig 14 2 Press Next until Service Menu 341 Enable Disable PIN Access appears in the display Default value 00 appears below Service Menu 3 In Service Menu 341 press to change digit flashing value to 01 see Fig 14 note selecting 01 enables PIn access for the thermostat service menus...

Страница 6: ...ntrols heating fan 130 Changeover valve B O terminal 0 1 0 0 B O terminal controls valve in cooling 1 B O terminal controls valve in heating 140 Auxiliary Heat 0 1 0 0 Electric backup heat 1 Fossil fuel backup heat 150 Backlight 0 1 0 0 Backlight temporarily on 1 Backlight always on low intensity 24V only 170 Remote Sensor 0 1 0 Select sensor if used connected to the S1 Terminal Contact PECO for m...

Страница 7: ...eduled event 1 1 Hour 2 2 Hours 3 3 Hours 4 4 Hours 400 Cycles Per Hour CPH Cooling Stage 1 0 6 CPH 3 CPH Defines the number of cycles per hour for cooling Stage 1 Select 0 to enable ON OFF control for Stage 1 cooling 410 Cycles Per Hour CPH Cooling Stage 2 0 6 CPH 3 CPH Defines the number of cycles per hour for cooling Stage 2 Select 0 to enable ON OFF control for Stage 2 cooling 420 Cycles Per H...

Страница 8: ...Disable 1 Enable Note Press Done key to complete process 600 System Test Main Output Cool 0 2 0 Select an option to activate the fan output for 10 minutes select 0 Done or a different Service Menu to disable 0 Disable Default 1 Cool Stage 1 2 Cool Stage 2 610 System Test Main Output Heat 0 3 0 Select an option to activate the fan output for 10 minutes select 0 Done or a different Service Menu to d...

Страница 9: ...resent check wire connection between the heating equipment and the thermostat If Demand Indicator light is red Heating is occurring No action is required If Demand Indicator light is green Cooling is occurring No action is required If Demand Indicator light is flashing An error has occurred Remote sensor may be malfunctioning Check remote sensor wiring Verify that the sensor s are PECO supported p...

Страница 10: ...Unt Peco InDoor remote zone sensor sP155 017 warnInG READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL OPERATE OR SERVICE THIS SENSOR Failure to observe safety information and comply with instructions could result in PERSONAL INJURY DEATH AND OR PROPERTY DAMAGE To avoid electrical shock or damage to equipment disconnect power before installing and use only wiring with insulation rated...

Страница 11: ...sor maXImUm lenGth anD wIre sIze Distance from Unit to control recommended wire size 000 150 feet 22 gauge 151 240 feet 20 gauge 241 385 feet 18 gauge 386 610 feet 16 gauge 611 970 feet 14 gauge wIrInG 1 run wires Run wires between the thermostat wallplate and the Zone Sensor subbase 2 connect wires Connect the wiring to the terminals S1 and SC at the thermostat wallplate see Fig 22 note See TABLE...

Страница 12: ...or message If the Indoor Remote Zone Sensor is not connected properly check the following Make sure sensor is wired properly and connected to terminals S1 and SC on the thermostat wallplate see Table 1 Terminal Designations and System Types If using multiple sensors make sure wiring follows diagrams in Sensor Wiring for Temperature Averaging Make sure to select 01 in Service Menu 170 Figure 25 The...

Отзывы: