Peco Perfomance PRO T4500 Скачать руководство пользователя страница 2

© COPYRIGHT 2010 PECO, INC.  ALL RIGHTS RESERVED.   

 

 

 

P/N 70476 3220-2265 REV 00

2

Part I: Install the wallPlate

1.  Position the wallplate on the wall with the directional arrow pointing up (see Fig. 3) and 

terminal blocks facing outward. 

2.  Pull equipment wires through the wallplate wiring passage (see Fig. 3).

3.  Use a level to determine the best horizontal wallplate mounting position. 

4.  Mark positions of the screw holes (two at minimum) with a pencil and remove wallplate. 

5.  Drill holes at pencil-marked locations (3/16” for drywall, 7/32” for plaster).

6.  Insert the wall anchors in the holes, tapping them into place.

7.  Mount the wallplate onto the wall and insert screws through mounting holes. Assure 

that all loose wires come through the center opening of the backplate (see Fig. 3).

8.  Cap off any unused wires and terminate properly according to local building codes. 

Part II: attach wIres to thermostat wallPlate

1.  Select the terminal designations that correspond to the system type (see Table 1).

Conventional Terminal Letters

Heat Pump Terminal Letters

c

Unswitched side, 24 VAC

c

Unswitched side, 24 VAC

w1

Stage 1 Heat

B/o

Reversing Valve

w2

Stage 2 Heat

aUX

Auxiliary (Stage 3 Heat)

G

Fan

G

Fan

a

a

e

e

Y1

Stage 1 Cool

Y1

Compressor Stage 1, Heat /Cool 1

Y2

Stage 2 Cool (or 

Dehumidify)

Y2

Compressor Stage 2, Heat /Cool 2  

(or Dehumidify) 

rh

Power for heating,  

switched side, 24 VAC

rh

Power for heating, 

switched side, 24 VAC

rc

Power for cooling,  

switched side, 24 VAC

rc

Power for cooling,  

switched side, 24 VAC

sc

Sensor Common

sc

Sensor Common

s1

Indoor Remote Sensor

s1

Indoor Remote Sensor

System Type 1: 1H/1C Conventional

System Type 2: 1H/1C Heat Pump

TERM

Function

TERM

Function

C

Common

C

Common

W1

Heat

B/O

Reversing Valve 

W2

AUX

G

Fan

G

Fan

A

A

E

E

Y1

Cool

Y1

Compressor

Y2

Y2

RH

Power for Heating 

RH

Power for Heating 

RC

Power for Cooling

RC

Power for Cooling

System Type 3: Heat only (without fan)

System Type 4: Heat only with fan

TERM

Function

TERM

Function

C

Common

C

Common

W1

Heat

W1

Heat

W2

W2

G

G

Fan

A

A

E

E

Y1

Y1

Y2

Y2

RH

Power for Heating

RH

Power for Heating

RC

RC

System Type 5: Cool only

System Type 6: 2H/1C Heat Pump (Aux.)

TERM

Function

TERM

Function

C

Common

C

Common

W1

B/O

Reversing Valve

W2

AUX

Auxiliary Heat

G

Fan

G

Fan

A

A

E

E

Y1

Cool

Y1

Compressor

Y2

Y2

RH

Power for Heating 

RH

Power for Heating

RC

Power for Cooling 

RC

Power for Cooling 

System Type 7: 2H/2C Conventional

System Type 8: 2H/1C Conventional

TERM

Function

TERM

Function

C

Common

C

Common

W1

Heat 1

W1

Heat 1

W2

Heat 2

W2

Heat 2

G

Fan

G

Fan

A

A

E

E

Y1

Cool 1

Y1

Cool

Y2

Cool 2

Y2

RH

Power for Heating

RH

Power for Heating

RC

Power for Cooling

RC

Power for Cooling

all electrIcal loaDs 

mUst Be connecteD to 

termInal c (24 vac).

i

*note

: See “PECO Compatible Accessories” 

in Operating Manual to learn about additional 

sensor applications.

▲ 

!

• warnInG: Disconnect power before beginning installation.

• caUtIon: Use copper wire only. Insulate or wire-nut all unused leads.

• Use care to avoid electrostatic discharge to thermostat

taBle 1. termInal DesIGnatIons anD sYstem tYPes 

Figure 3.

Position 

the wallplate

on the wall. 

Pull wires 

through 

wiring passage.

wiring passage

terminal blocks enlarged

Содержание Perfomance PRO T4500

Страница 1: ...nd heat pump applications System mode selections Off Heat Cool Auto Stages 1 Heat 1 Cool 2 Heat 1 Cool 1 Heat 2 Cool 2 Heat 2 Cool 3 Heat 2 Cool Fan control Cycling Auto or Continuous On 1 Speed Permanent memory All device settings are stored in permanent memory Connections for Remote Sensors indoor and occupancy caUtIon 24 vac low voltage thermostat Do not install on voltages higher than 30 vac U...

Страница 2: ... side 24 VAC sc Sensor Common sc Sensor Common s1 Indoor Remote Sensor s1 Indoor Remote Sensor System Type 1 1H 1C Conventional System Type 2 1H 1C Heat Pump TERM Function TERM Function C Common C Common W1 Heat B O Reversing Valve W2 AUX G Fan G Fan A A E E Y1 Cool Y1 Compressor Y2 Y2 RH Power for Heating RH Power for Heating RC Power for Cooling RC Power for Cooling System Type 3 Heat only witho...

Страница 3: ...allplate Assure that the metal jumper connects RC and RH Connect power side to the RC RH and assure that the jumper remains in place two transformer system The T4000 T4500 is shipped with a jumper connecting terminals RH and RC If the heating and cooling equipment do not use separate transformers leave this jumper in place If separate transformers are required remove this jumper With the jumper re...

Страница 4: ...wIth sYstem tests System test verification is highly recommended to verify thermostat operation Follow at least one procedure in the system tests below Refer to the Service Menus see Table 2 for more tests For all tests press next to continue to the following system test which is the next available Service Menu Press Done only if finished performing all system tests Pressing Done exits the Service...

Страница 5: ...ostat press the lower left and lower right keys simultaneously for about five seconds Next Go Back and Done appear see Fig 14 2 Press Next until Service Menu 341 Enable Disable PIN Access appears in the display Default value 00 appears below Service Menu 3 In Service Menu 341 press to change digit flashing value to 01 see Fig 14 note selecting 01 enables PIn access for the thermostat service menus...

Страница 6: ...ntrols heating fan 130 Changeover valve B O terminal 0 1 0 0 B O terminal controls valve in cooling 1 B O terminal controls valve in heating 140 Auxiliary Heat 0 1 0 0 Electric backup heat 1 Fossil fuel backup heat 150 Backlight 0 1 0 0 Backlight temporarily on 1 Backlight always on low intensity 24V only 170 Remote Sensor 0 1 0 Select sensor if used connected to the S1 Terminal Contact PECO for m...

Страница 7: ...eduled event 1 1 Hour 2 2 Hours 3 3 Hours 4 4 Hours 400 Cycles Per Hour CPH Cooling Stage 1 0 6 CPH 3 CPH Defines the number of cycles per hour for cooling Stage 1 Select 0 to enable ON OFF control for Stage 1 cooling 410 Cycles Per Hour CPH Cooling Stage 2 0 6 CPH 3 CPH Defines the number of cycles per hour for cooling Stage 2 Select 0 to enable ON OFF control for Stage 2 cooling 420 Cycles Per H...

Страница 8: ...Disable 1 Enable Note Press Done key to complete process 600 System Test Main Output Cool 0 2 0 Select an option to activate the fan output for 10 minutes select 0 Done or a different Service Menu to disable 0 Disable Default 1 Cool Stage 1 2 Cool Stage 2 610 System Test Main Output Heat 0 3 0 Select an option to activate the fan output for 10 minutes select 0 Done or a different Service Menu to d...

Страница 9: ...resent check wire connection between the heating equipment and the thermostat If Demand Indicator light is red Heating is occurring No action is required If Demand Indicator light is green Cooling is occurring No action is required If Demand Indicator light is flashing An error has occurred Remote sensor may be malfunctioning Check remote sensor wiring Verify that the sensor s are PECO supported p...

Страница 10: ...Unt Peco InDoor remote zone sensor sP155 017 warnInG READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL OPERATE OR SERVICE THIS SENSOR Failure to observe safety information and comply with instructions could result in PERSONAL INJURY DEATH AND OR PROPERTY DAMAGE To avoid electrical shock or damage to equipment disconnect power before installing and use only wiring with insulation rated...

Страница 11: ...sor maXImUm lenGth anD wIre sIze Distance from Unit to control recommended wire size 000 150 feet 22 gauge 151 240 feet 20 gauge 241 385 feet 18 gauge 386 610 feet 16 gauge 611 970 feet 14 gauge wIrInG 1 run wires Run wires between the thermostat wallplate and the Zone Sensor subbase 2 connect wires Connect the wiring to the terminals S1 and SC at the thermostat wallplate see Fig 22 note See TABLE...

Страница 12: ...or message If the Indoor Remote Zone Sensor is not connected properly check the following Make sure sensor is wired properly and connected to terminals S1 and SC on the thermostat wallplate see Table 1 Terminal Designations and System Types If using multiple sensors make sure wiring follows diagrams in Sensor Wiring for Temperature Averaging Make sure to select 01 in Service Menu 170 Figure 25 The...

Отзывы: