Peco Perfomance PRO T4500 Скачать руководство пользователя страница 11

© COPYRIGHT 2010 PECO, INC.  ALL RIGHTS RESERVED.   

 

 

 

P/N 70476 3220-2265 REV 00 

11

InstallatIon

1. 

mounting location. 

Choose a location on an interior wall near the air return grille, 

about fi ve feet above fl oor level, where air circulation is good and temperature is 

average for the zone. 

avoid

 mounting the indoor zone sensor in areas such as: 

• Behind doors

• On outside walls, or any walls with unheated or uncooled areas behind the zone 

sensor

• In direct sunlight, or near any source of radiant heat that could affect the 

temperature measurements

• In line with the discharge air from the unit being controlled 

2.  mount subbase

. Remove Zone Sensor cover from the subbase and mount subbase 

on the wall or in a 2’ X 4” device box. Route the wires through the wire access hole in 

the subbase (see Fig. 21). Seal the hole in the wall behind the subbase. 

taBle 4. zone sensor maXImUm lenGth anD wIre sIze

Distance from Unit to control

recommended wire size

000 - 150 feet

22 gauge

151 - 240 feet

20 gauge

241- 385 feet

18 gauge

386 - 610 feet

16 gauge

611 -970 feet

14 gauge

wIrInG

1. 

run wires. 

Run wires between the thermostat wallplate and the Zone Sensor subbase. 

2. 

connect wires.

 Connect the wiring to the terminals, S1 and SC, at the thermostat 

wallplate (see Fig. 22). 

note:

 See TABLE 1 for terminal designations for the Indoor Remote Zone Sensor.

3. 

replace cover. 

Place Zone Sensor cover back on the subbase, and snap it securely 

into place. 

4. 

Go to service menu 170. 

Select option “01”  to enable the Indoor Sensor (see Fig. 23). 

Figure 21. 

Mounting the 

SP155-017

Indoor Temperature 

Zone Sensor

Device box mounting

Wall mounting

Terminal S1

Terminal SC

Figure 22. 

Wiring terminal 

designations for 

SP155-017

Indoor Remote 

Zone Sensor.

Figure 23.  

Service Menu 

170  allows 

the user 

to enable 

the Indoor 

Remote Zone  

Sensor. 

 

caUtIon

: Keep wires separate and routed away from any source of 

noise such as motors, fl uorescent lights, and other wiring.

▲ 

!

Содержание Perfomance PRO T4500

Страница 1: ...nd heat pump applications System mode selections Off Heat Cool Auto Stages 1 Heat 1 Cool 2 Heat 1 Cool 1 Heat 2 Cool 2 Heat 2 Cool 3 Heat 2 Cool Fan control Cycling Auto or Continuous On 1 Speed Permanent memory All device settings are stored in permanent memory Connections for Remote Sensors indoor and occupancy caUtIon 24 vac low voltage thermostat Do not install on voltages higher than 30 vac U...

Страница 2: ... side 24 VAC sc Sensor Common sc Sensor Common s1 Indoor Remote Sensor s1 Indoor Remote Sensor System Type 1 1H 1C Conventional System Type 2 1H 1C Heat Pump TERM Function TERM Function C Common C Common W1 Heat B O Reversing Valve W2 AUX G Fan G Fan A A E E Y1 Cool Y1 Compressor Y2 Y2 RH Power for Heating RH Power for Heating RC Power for Cooling RC Power for Cooling System Type 3 Heat only witho...

Страница 3: ...allplate Assure that the metal jumper connects RC and RH Connect power side to the RC RH and assure that the jumper remains in place two transformer system The T4000 T4500 is shipped with a jumper connecting terminals RH and RC If the heating and cooling equipment do not use separate transformers leave this jumper in place If separate transformers are required remove this jumper With the jumper re...

Страница 4: ...wIth sYstem tests System test verification is highly recommended to verify thermostat operation Follow at least one procedure in the system tests below Refer to the Service Menus see Table 2 for more tests For all tests press next to continue to the following system test which is the next available Service Menu Press Done only if finished performing all system tests Pressing Done exits the Service...

Страница 5: ...ostat press the lower left and lower right keys simultaneously for about five seconds Next Go Back and Done appear see Fig 14 2 Press Next until Service Menu 341 Enable Disable PIN Access appears in the display Default value 00 appears below Service Menu 3 In Service Menu 341 press to change digit flashing value to 01 see Fig 14 note selecting 01 enables PIn access for the thermostat service menus...

Страница 6: ...ntrols heating fan 130 Changeover valve B O terminal 0 1 0 0 B O terminal controls valve in cooling 1 B O terminal controls valve in heating 140 Auxiliary Heat 0 1 0 0 Electric backup heat 1 Fossil fuel backup heat 150 Backlight 0 1 0 0 Backlight temporarily on 1 Backlight always on low intensity 24V only 170 Remote Sensor 0 1 0 Select sensor if used connected to the S1 Terminal Contact PECO for m...

Страница 7: ...eduled event 1 1 Hour 2 2 Hours 3 3 Hours 4 4 Hours 400 Cycles Per Hour CPH Cooling Stage 1 0 6 CPH 3 CPH Defines the number of cycles per hour for cooling Stage 1 Select 0 to enable ON OFF control for Stage 1 cooling 410 Cycles Per Hour CPH Cooling Stage 2 0 6 CPH 3 CPH Defines the number of cycles per hour for cooling Stage 2 Select 0 to enable ON OFF control for Stage 2 cooling 420 Cycles Per H...

Страница 8: ...Disable 1 Enable Note Press Done key to complete process 600 System Test Main Output Cool 0 2 0 Select an option to activate the fan output for 10 minutes select 0 Done or a different Service Menu to disable 0 Disable Default 1 Cool Stage 1 2 Cool Stage 2 610 System Test Main Output Heat 0 3 0 Select an option to activate the fan output for 10 minutes select 0 Done or a different Service Menu to d...

Страница 9: ...resent check wire connection between the heating equipment and the thermostat If Demand Indicator light is red Heating is occurring No action is required If Demand Indicator light is green Cooling is occurring No action is required If Demand Indicator light is flashing An error has occurred Remote sensor may be malfunctioning Check remote sensor wiring Verify that the sensor s are PECO supported p...

Страница 10: ...Unt Peco InDoor remote zone sensor sP155 017 warnInG READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL OPERATE OR SERVICE THIS SENSOR Failure to observe safety information and comply with instructions could result in PERSONAL INJURY DEATH AND OR PROPERTY DAMAGE To avoid electrical shock or damage to equipment disconnect power before installing and use only wiring with insulation rated...

Страница 11: ...sor maXImUm lenGth anD wIre sIze Distance from Unit to control recommended wire size 000 150 feet 22 gauge 151 240 feet 20 gauge 241 385 feet 18 gauge 386 610 feet 16 gauge 611 970 feet 14 gauge wIrInG 1 run wires Run wires between the thermostat wallplate and the Zone Sensor subbase 2 connect wires Connect the wiring to the terminals S1 and SC at the thermostat wallplate see Fig 22 note See TABLE...

Страница 12: ...or message If the Indoor Remote Zone Sensor is not connected properly check the following Make sure sensor is wired properly and connected to terminals S1 and SC on the thermostat wallplate see Table 1 Terminal Designations and System Types If using multiple sensors make sure wiring follows diagrams in Sensor Wiring for Temperature Averaging Make sure to select 01 in Service Menu 170 Figure 25 The...

Отзывы: