To change the Alarm Type select the Alarm Type button for the relay and select, from the list,
the alarm type required. The following alarm types are available:
•
Warning Alarm
•
Limit Alarm
•
Comms Error
•
Self Test Fail
•
Test Running
•
Maintenance
•
Zero/Span Fail
•
Contam Fail
To allocate the device select the Device button for the relay and select the device required.
Select ‘Back’ to return to the ‘Setup’ display.
If it is required for alarms to stay latched after the end of an alarm condition use the Latch Alarm
function:
Select ‘Setup’ display
Menu route:
Other Functions
↵
Latch Alarms?
The relays can be put in a failsafe mode. In this mode during normal non-alarm conditions the
relays are energised and de-energised when an alarm is generated. In the event of a power
failure of a power loss to the Control Unit the relays will de-energise and alarms generated.
Select ‘Setup’ display
Menu route:
Other Functions
↵
FailSafe Relays?
Relay Settings
Alarm Type
1
2
3
Limit Alarm
Limit Alarm
Limit Alarm
Back
4
Limit Alarm
Stack 1 Dust
Stack 2 Dust
Stack 3 Dust
Stack 4 Dust
Device