8. SIGNAL PROCESSOR WARNING MESSAGES
8.1.
INPUT PRESSURE OVERRANGE MESSAGE
If the input pressure exceeds the entered Op. Range value, the following message will appear on the
display. It will alternate between the process display and the error message until the input falls below
the Op. Range value.
- Caution -
Input Beyond
Operating Range
Selected
8.2. TRANSDUCER
CALIBRATION MESSAGE
If during a transducer zero or span calibration process, the transducer output pressure value measured
exceeds ± 20% of the expected value, the following message will appear on the display. Once the
Enter button is pressed, the display returns to the previous calibration menu.
Value entered is
Outside Factory
set limits
(Press Enter)
8.3.
AREA FACTOR MESSAGE
If the new value entered for Area Factor causes the Op. Range value to exceed the new calculated Max.
Full Scale value, the following message will appear on the display.
Op Range Outside
Allowable Value.
Will be Reset
to MAX F.S.