OAFE-1550 Operation & Maintenance Manual
Paragon Controls Incorporated
21
Revision Level 000
7. SIGNAL PROCESSOR TECH CONFIG. MENUS
To enter the Tech Configuration Menu, press
UP/DOWN
buttons simultaneously, enter password
number 1000 and press the enter button.
7.1. AREA
FACTOR
Allows user to enter or modify an existing Area Factor. If a new Area Factor value is entered and causes
the previous entered Op. Range value to exceed the new minimum and maximum calculated Full Scale
range, the message shown in section 2.5.1 will appear.
Tech. Config.
Password: 0000
Area Factor
Area Factor
Zero Calibration
(FT
2
)
50% Calibration
(001.000)
Span Calibration
(Press Enter)
7.2. MIN.
CALIBRATION
The Min. Calibration menu allows a user to perform a min. transducer calibration. This value will be
placed in a different memory location and used until a Return to Factory Defaults is selected (section
5.20).
Tech.
Config.
Password:
0000
Area Factor
Input Value
CPU Taking
Zero Calibration
(0.0000) in. W.C.
Samples
50%
Calibration
Span Calibration
(Press Enter)
(Please
Wait)
7.3.
50% CALIBRATION - DISPLAYED ONLY IN PRESSURE MONITOR
MODE
The 50% Calibration menu allows a user to perform a 50% transducer calibration to eliminate zero drift
in a bipolar transducer. This value will be placed in a different memory location then the factory zero
memory location (section 5.20).
Tech.
Config.
Password:
0000
Area Factor
Input Value
CPU Taking
Zero Calibration
(0.0285) inch w.c.
Samples
50% Calibration
Span Calibration
(Press Enter)
(Please
Wait)