OAFE-1550 Operation & Maintenance Manual
Paragon Controls Incorporated
9
Revision Level 000
Warning Message:
Op Range Outside
allowable Value
Op Range will be
reset to the MAX
F.S. value
If the new Area Factor causes the existing Operating Range value to be outside the new calculated Min.
or Max Full Scale value, the Operating Range will be reset to the new Max Full Scale value. The
display will automatically jump to the Op Range menu allowing the user to enter a new Operating
Range value. This can be accomplished by performing the steps under Section 2.5.2 Operating Range.
3.5.2. Operating
Range
The Operating Range allows the user to enter a value which will represent 100% of the process output
signal. The menu will display the Maximum Full Scale value possible for the user to enter as the
Operating Range. The Operating Range can be changed by using the following steps:
Step 1.
From the active display, enter the Field menu by pressing and holding the Enter button
for 3 seconds.
Step 2.
Press the Enter button once to access the Operating Range menu.
Step 3.
Enter new Operating Range using Up/Down/Left/Right buttons.
Step 4.
Press the Enter button once.
Step 5.
Press ESC button twice.
Step 6.
The active display should now be displayed.
Step 7.
Process Output is automatically rescaled to the new Operating Range.
Field Setup
Menu
Operating Range
Operating Range
Zero Calibration
(6,000-12,000)SCFM
Engineering Units
Enter Value
Lockdown
(10,000)
SCFM