OAFE-1550 Operation & Maintenance Manual
Paragon Controls Incorporated
8
Revision Level 000
3.4. INPUT/OUTPUT
SET-UP
The MicroTrans
EQ
has been configured and calibrated at the factory for your specific requirements.
Refer to MicroTrans
EQ
Set-Up label located on the left side of unit to verify correct Input/Output
configuration for the application. Refer to chart and Figure 3.2 above if input or output configuration
changes are required.
3.4.1. Process
output
To change the output configuration, set the S2 & S4 switches as follows:
Process Output
Range
S2
S4
Current
4-20mA
NA mA
Voltage
0-10vdc
10V
V
Voltage
0-5vdc
5V
V
3.4.2. Temperature Input (Option)
To change the input configuration, set the S1 switch as follows:
Temperature Input
S1 Switch Selection
4-20mA mA
0-10VDC V
3.5.
COMMON CONFIGURATION CHANGES
3.5.1. Area
Factor
Allows user to enter or modify an existing Area Factor. The area factor can be entered or modified as
follows:
Step 1.
From the active display, enter the Tech. Config. menu by pressing the Up/Down
buttons simultaneously.
Step 2.
Enter password number 1000 and press Enter button.
Step 3.
Press the Enter Button once to access the Area Factor menu.
Step 4.
Enter new Area Factory using Up/Down/Left/Right buttons.
Step 5.
Press Enter button once.
Step 6.
Press ESC button once.
Step 7.
The active display should now be displayed.
Tech. Config.
Password: 1000
Area Factor
Area Factor
Zero Calibration
(FT
2
)
50% Calibration
(001.000)
Span Calibration
(Press Enter)