The menus are:

BASE 

 

Set the Date, Time, Temperatures, and Timer function.  Readouts 

W.PR. 

Weekly Program 

There are 6 time periods that can be set to begin a day, night,                   

 

 

 

or economy period.  Each time can be set to begin on any day    

 

 

 

or combination of days of the week.

D.PRO 

Date Program 

There are 8 dates that can be set so that four different day, night,  

 

 

 

or economy periods can be set to begin and end in advance.  

 

 

 

 

A date setting overrides a weekly setting.

X.OUT 

Extra Output 

This is an output that can be activated by temperature and/or time.

LOG 

Log Values 

Running log of the outdoor temperature (or room temperature if it  

 

 

 

is connected) for up to 96 events at intervals of up to 255 minutes.

REGUL 

Control parameters 

Minimum & maximum supply temperatures, proportional bands and  

  

 

integral 

times

RET.R 

Return 

Sets the minimum return water temperature

CURVE 

Curve selection 

Select the outdoor curve. 

RET.R 

Outputs 

Control type, outdoor cutoff temperature

INPUt 

10 

Inputs 

External contact function, internal sensor

PUMP 

11 

Pump Control 

The pump can be controlled by outdoor or supply water temperature.

CAL 

12 

Calibration 

Adjustment of the sensors to compensate for small errors in the sensor 

 

 

 

or to compensate for the length of wire to the sensor.  Adjust the clock  

 

 

 

speed if it is running fast or slow, set the beginning and end of 

 

 

 

 

daylight savings time, and set the clock for 12 or 24 hour time.     

 

 

 

Set temperatures in Fahrenheit or Celsius.

BUT.F 

13 

Button Functions 

Security, locking, limits on settings, display

Test 

14 

Test 

Manually operate outputs, simulate temperatures, set security code

TYPE 

15 

TYPE 

This displays data about this particular controller.  There are no   

  

 

programmable 

functions.

KOMM 16 

Communication  ModBus

12

Содержание TC 204

Страница 1: ...which is the default program Some not frequently used functions are not covered in this manual Instructions for these as well as for all other programs are available at www paxtoncorp com Other progra...

Страница 2: ...The TC 204 can be removed from the steel box cover and the external terminal board for installation directly in an occupied space Loosen the connector on the circuit board and then the center screw u...

Страница 3: ...Optional Supply Water Sensor Outdoor Sensor 24 Volts ac Power 25 va minimum If the valve turns in the wrong direction reverse the brown black wires on the VM62 actuator Outdoor Reset Control with the...

Страница 4: ...stop use external relay 4 input for remote operation 5 Output to actuator 24 Vac 6 Common 6 Common 7 Return water or room sensor optional 8 Supply water sensor must be used 9 Outdoor sensor 10 Auxili...

Страница 5: ...roll to the menu with the function you want Once you select a value in a line it is permanently set when you press or You leave programming by pressing and holding the key Outdoor Reset Programming Mo...

Страница 6: ...Then the valve closes MAXW 41 F 203 F Default 140 F 60 C When you set the maximum temperature the supply temperature never rises above the setting Proportional Band P W 0 5 C 99 5 C Default 60 C Leave...

Страница 7: ...10C1 at 86 At 50 F outside the supply temperature will be 86 F Set 10C1 so that at the outside design temperature in your area the supply temperature will be near the maxi mum temperature allowed in...

Страница 8: ...ng in LIM 0 MOT 0 30 Days Default 7 days The pump can run for 3 minutes at night without regard to the settings in LIM 0 LIM 1 above The purpose is to prevent seals from drying out The intervals can b...

Страница 9: ...e symbol does not appear Setting the Clock Menu 1 BASE Use the key to scroll to a line for time that looks like this WED 02 35 Two dots between hr min mean am three dots pm Use the UP or DOWN key to m...

Страница 10: ...In 12 hour time PM is indicated by 3 dots between hours minutes Days of the week are at the lower left of the screen in a row of 7 dots or vertical lines Monday is day 1 and Sunday is day 7 A vertical...

Страница 11: ...onth and the second is the day of the month The clock will move forward one hour at 2 00 am on the date you set WIN Month 1 12 Day 1 31 End Daylight Savings Time Set it the same way as SUM above If yo...

Страница 12: ...rtional bands and integral times RET R 7 Return Sets the minimum return water temperature CURVE 8 Curve selection Select the outdoor curve RET R 9 Outputs Control type outdoor cutoff temperature INPUt...

Отзывы: