Relay 24 vac coil
spst no

1
2
3
4
5
6
6
7
8
9

10

6

11
12

5
6

Black
(counterclockwise)

Brown
(Clockwise)

Blue
(Common)

VM62 Actuator

Room or Return Sensor
(Optional)

Supply Water Sensor

Outdoor Sensor

24 Volts ac Power
25 va minimum

If the valve turns in the wrong 
direction, reverse the brown & 
black wires on the VM62 actuator

Outdoor Reset Control with     
the VM62 Actuator.

3

1
2
3
4
5
6
6
7
8
9

10

6

11
12

5
6

Pump

Line

N

Pump Control

Sensor wires can be lengthened 
with thermostat wire to maximum 
250 feet.

Содержание TC 204

Страница 1: ...which is the default program Some not frequently used functions are not covered in this manual Instructions for these as well as for all other programs are available at www paxtoncorp com Other progra...

Страница 2: ...The TC 204 can be removed from the steel box cover and the external terminal board for installation directly in an occupied space Loosen the connector on the circuit board and then the center screw u...

Страница 3: ...Optional Supply Water Sensor Outdoor Sensor 24 Volts ac Power 25 va minimum If the valve turns in the wrong direction reverse the brown black wires on the VM62 actuator Outdoor Reset Control with the...

Страница 4: ...stop use external relay 4 input for remote operation 5 Output to actuator 24 Vac 6 Common 6 Common 7 Return water or room sensor optional 8 Supply water sensor must be used 9 Outdoor sensor 10 Auxili...

Страница 5: ...roll to the menu with the function you want Once you select a value in a line it is permanently set when you press or You leave programming by pressing and holding the key Outdoor Reset Programming Mo...

Страница 6: ...Then the valve closes MAXW 41 F 203 F Default 140 F 60 C When you set the maximum temperature the supply temperature never rises above the setting Proportional Band P W 0 5 C 99 5 C Default 60 C Leave...

Страница 7: ...10C1 at 86 At 50 F outside the supply temperature will be 86 F Set 10C1 so that at the outside design temperature in your area the supply temperature will be near the maxi mum temperature allowed in...

Страница 8: ...ng in LIM 0 MOT 0 30 Days Default 7 days The pump can run for 3 minutes at night without regard to the settings in LIM 0 LIM 1 above The purpose is to prevent seals from drying out The intervals can b...

Страница 9: ...e symbol does not appear Setting the Clock Menu 1 BASE Use the key to scroll to a line for time that looks like this WED 02 35 Two dots between hr min mean am three dots pm Use the UP or DOWN key to m...

Страница 10: ...In 12 hour time PM is indicated by 3 dots between hours minutes Days of the week are at the lower left of the screen in a row of 7 dots or vertical lines Monday is day 1 and Sunday is day 7 A vertical...

Страница 11: ...onth and the second is the day of the month The clock will move forward one hour at 2 00 am on the date you set WIN Month 1 12 Day 1 31 End Daylight Savings Time Set it the same way as SUM above If yo...

Страница 12: ...rtional bands and integral times RET R 7 Return Sets the minimum return water temperature CURVE 8 Curve selection Select the outdoor curve RET R 9 Outputs Control type outdoor cutoff temperature INPUt...

Отзывы: