Paxton TC 204 Скачать руководство пользователя страница 11

Optimization

Menu   2 

W.PR

OPT1   

0 - 40   

Default 20 

Skip this line initially.

The colder it is outside and/or the further the room temperature is below set point the sooner the controller will 
start the warm-up cycle. The number in this line is a constant in the equation the TC204 uses to calculate the 
warm-up time.  If the building warms up too soon, lower it to 15; if the building isnʼt warm soon enough, increase 
this number to 25.  If you set this line to 0 there is no warm-up cycle at all.

Calibration

Menu 12 

CAL.

You can calibrate the temperature sensors used in the TC204.
R1 

 

-9.5 to 9.5 degrees

Room Temperature Sensor Calibration

R2 

 

-9.5 to 9.5 degrees

Second Room Temperature (if used)

OUTD   

-9.5 to 9.5 degrees

Outdoor Temperature Sensor Calibration.

SEC/D   

-9.9 to 9.9 seconds per day

If the clock runs fast or slow it can be adjusted here.  If it is slow add a positive adjustment.  If the clock gains one 
minute per month, make the adjustment -2.0.

Daylight Savings Time

Menu 12 

CAL

SUM 

 

Month 1 - 12 

Day 1 - 31

Begin Daylight Savings Time.  The first pair of digits is the month and the second is the day of the month.         
The clock will move forward one hour at 2:00 am on the date  you set.

WIN 

 

Month 1 - 12 

Day 1 - 31

End Daylight Savings Time.  Set  it the same way as SUM above.  If you donʼt want daylight savings time set both 
SUM & WIN to 0000.

Time

Menu 12 

CAL

24h 

 

0 or 1   

Default 0 (12 hour time)

Set this to 1 if you want 24 hour (military) time, 0 for 12 hour time.  In 12 hour time P.M. shows as 3 dots between 
the hours and minutes.

Temperature Scale

SEL.ºF   

0 or 1   

Default 1 (F)

Set this to 1 if you want readouts in Fahrenheit.  Not all temperatures can be set or read in F.

O.RES   

0 or 1

The readout of the minimum outdoor temperature can be reset manually or automatically.  If you want the readout 
to reset automatically every day set this line to 1.

Date Program

Menu 3  

D.PRO

 

You can set up to 4 events that override the weekly program.  These can be set up to a year in advance.  You 
can, for example, set a long term setback for a vacation.

Extra Output

Menu 4  

X.OUT

There is an extra output that can be activated by either time or outdoor temperature or both.

Logging Measured Values 

Menu 5  

LOG

You can keep a log of up to 96 values of the outdoor temperature or the supply water temperature or the room 
temperature at intervals up to 1 hour apart.

11

Содержание TC 204

Страница 1: ...which is the default program Some not frequently used functions are not covered in this manual Instructions for these as well as for all other programs are available at www paxtoncorp com Other progra...

Страница 2: ...The TC 204 can be removed from the steel box cover and the external terminal board for installation directly in an occupied space Loosen the connector on the circuit board and then the center screw u...

Страница 3: ...Optional Supply Water Sensor Outdoor Sensor 24 Volts ac Power 25 va minimum If the valve turns in the wrong direction reverse the brown black wires on the VM62 actuator Outdoor Reset Control with the...

Страница 4: ...stop use external relay 4 input for remote operation 5 Output to actuator 24 Vac 6 Common 6 Common 7 Return water or room sensor optional 8 Supply water sensor must be used 9 Outdoor sensor 10 Auxili...

Страница 5: ...roll to the menu with the function you want Once you select a value in a line it is permanently set when you press or You leave programming by pressing and holding the key Outdoor Reset Programming Mo...

Страница 6: ...Then the valve closes MAXW 41 F 203 F Default 140 F 60 C When you set the maximum temperature the supply temperature never rises above the setting Proportional Band P W 0 5 C 99 5 C Default 60 C Leave...

Страница 7: ...10C1 at 86 At 50 F outside the supply temperature will be 86 F Set 10C1 so that at the outside design temperature in your area the supply temperature will be near the maxi mum temperature allowed in...

Страница 8: ...ng in LIM 0 MOT 0 30 Days Default 7 days The pump can run for 3 minutes at night without regard to the settings in LIM 0 LIM 1 above The purpose is to prevent seals from drying out The intervals can b...

Страница 9: ...e symbol does not appear Setting the Clock Menu 1 BASE Use the key to scroll to a line for time that looks like this WED 02 35 Two dots between hr min mean am three dots pm Use the UP or DOWN key to m...

Страница 10: ...In 12 hour time PM is indicated by 3 dots between hours minutes Days of the week are at the lower left of the screen in a row of 7 dots or vertical lines Monday is day 1 and Sunday is day 7 A vertical...

Страница 11: ...onth and the second is the day of the month The clock will move forward one hour at 2 00 am on the date you set WIN Month 1 12 Day 1 31 End Daylight Savings Time Set it the same way as SUM above If yo...

Страница 12: ...rtional bands and integral times RET R 7 Return Sets the minimum return water temperature CURVE 8 Curve selection Select the outdoor curve RET R 9 Outputs Control type outdoor cutoff temperature INPUt...

Отзывы: