TC 204 Heating Controller

The TC204 is a multi-purpose heating controller with built-in programs for different types of heating systems.

General Data

Power requirement 

24 volts ac, 25 va

Inputs   

 

3 10k ohm ntc thermistors

 

 

  1 

digital

Outputs 

  3 

digital

   

 

 

2 analog 0 - 10 volt dc

This manual covers outdoor reset of hot water heating systems using a mixing valve and a 3-point  
floating actuator. For other applications see the expanded manual at www.paxtoncorp.com

Wiring

The diagrams show ESBE #62E (Paxton VM62) & 92-2M (Paxton VM92) valve actuators . These are 3-wire  
floating, 24 volt ac valve motors which fit ESBE 3-way & 4-way valves.
VM62 actuators are used with valve sizes 1/2” through 2”:  VM 92 actuators are used with valve sizes 2 1/2” - 6”.

Actuators of this type have a common wire.  Voltage applied between the common and one of the remaining wires 
drives the valve open and voltage between the common the the remaining wire drives the valve closed. If  no volt-
age is applied to either terminal the valve stays in place.

Other valves with different floating actuators may be used provided the voltage is 24 volts and the current draw 
of the actuator does not exceed the capacity of the TC204 (25 VA).  If these 2 conditions are not met the actuator 
must be operated through intermediate relays.

Programs

There are eight programs in the TC204.  This manual is for Program No.1 which is the default program.

Some not frequently used functions are not covered in this manual.  Instructions for these as well as for all other 
programs are available at: 
 

 

 

 

www.paxtoncorp.com

Other programs provide outdoor reset by modulating valves that accept a 0 - 10 volt dc signal, outdoor reset by 
direct boiler control, zone control without outdoor reset, and outdoor control of steam heating systems.

Program No. 1

Program 1 is

 

Supply Water Temperature Control using a 3-point floating valve actuator. The control mode can be        

Outdoor Reset 

with or without a room sensor, or direct control by room temperature only.

The supply temperature sensor must always be installed.
Outdoor reset is automatically initiated if the outdoor temperature sensor is installed.
Room temperature control is automatically initiated if the room temperature sensor is installed.
Additional functions are 

Pump Control

Auxiliary Output

, and

 Return Water Low Limit (see page 8)

.

Temperature Sensors

The supply water and outdoor air temperature sensors are included with the TC204.  A room temperature sensor 
is optional.  A room sensor is also built into the TC204, but to use it the TC204 must be installed in the controlled 
space.

1

Notes to the installer:

    1.  Program #1 - Outdoor reset control using a mixing valve, is the default program.

    2.  All defaults in program #1 will work in most cases.

    3.  Connect all sensors, the actuator wires and power supply. Set time & date (page 9)  

 

   

and let the system stabilize, before making any program changes.    

 

 

 

   

Nothing else needs to be done in most cases.

ver. 1.32-01

Содержание TC 204

Страница 1: ...which is the default program Some not frequently used functions are not covered in this manual Instructions for these as well as for all other programs are available at www paxtoncorp com Other progra...

Страница 2: ...The TC 204 can be removed from the steel box cover and the external terminal board for installation directly in an occupied space Loosen the connector on the circuit board and then the center screw u...

Страница 3: ...Optional Supply Water Sensor Outdoor Sensor 24 Volts ac Power 25 va minimum If the valve turns in the wrong direction reverse the brown black wires on the VM62 actuator Outdoor Reset Control with the...

Страница 4: ...stop use external relay 4 input for remote operation 5 Output to actuator 24 Vac 6 Common 6 Common 7 Return water or room sensor optional 8 Supply water sensor must be used 9 Outdoor sensor 10 Auxili...

Страница 5: ...roll to the menu with the function you want Once you select a value in a line it is permanently set when you press or You leave programming by pressing and holding the key Outdoor Reset Programming Mo...

Страница 6: ...Then the valve closes MAXW 41 F 203 F Default 140 F 60 C When you set the maximum temperature the supply temperature never rises above the setting Proportional Band P W 0 5 C 99 5 C Default 60 C Leave...

Страница 7: ...10C1 at 86 At 50 F outside the supply temperature will be 86 F Set 10C1 so that at the outside design temperature in your area the supply temperature will be near the maxi mum temperature allowed in...

Страница 8: ...ng in LIM 0 MOT 0 30 Days Default 7 days The pump can run for 3 minutes at night without regard to the settings in LIM 0 LIM 1 above The purpose is to prevent seals from drying out The intervals can b...

Страница 9: ...e symbol does not appear Setting the Clock Menu 1 BASE Use the key to scroll to a line for time that looks like this WED 02 35 Two dots between hr min mean am three dots pm Use the UP or DOWN key to m...

Страница 10: ...In 12 hour time PM is indicated by 3 dots between hours minutes Days of the week are at the lower left of the screen in a row of 7 dots or vertical lines Monday is day 1 and Sunday is day 7 A vertical...

Страница 11: ...onth and the second is the day of the month The clock will move forward one hour at 2 00 am on the date you set WIN Month 1 12 Day 1 31 End Daylight Savings Time Set it the same way as SUM above If yo...

Страница 12: ...rtional bands and integral times RET R 7 Return Sets the minimum return water temperature CURVE 8 Curve selection Select the outdoor curve RET R 9 Outputs Control type outdoor cutoff temperature INPUt...

Отзывы: