PARAM - WEIGHING PARAMETERS
The parameters in this menu allow to adjust the timing of the acquisition and updating of the display
and the manual or automatic zeroing that the transmitter performs.
f1Lt
WEIGHT FILTER
This parameter adjusts the refresh speed of the display and the
analog output.
Low values of the filter speed up the display refresh.
High values of the filter slow down the display refresh.
Value Updated Response
0
123 Hz
25 Hz
1
62 Hz
16 Hz
2
50 Hz
8 Hz
3
33 Hz
5 Hz
4
16 Hz
2.5 Hz
5
12 Hz
1.5 Hz
6
10 Hz
1 Hz
7
8 Hz
0.7 Hz
8
6 Hz
0.4 Hz
9
4 Hz
0.2 Hz
Default: 5
stab
WEIGHT STABILITY
This parameter defines the divisions number needed to deem the
weight stable.
A large number of divisions allows the transmitter to detect quickly
the weight stability, which is needed when executing tare and print
commands.
Value Change
0
Always stable weight
1
Stability reached quickly
2
Stability reached with medium parameters
3
Stability reached accurately
4
Stability reached with the highest accuracy
Default: 2
aut-O
AUTOZERO AT POWER ON
This parameter defines the maximum resettable weight upon power
on.
This operation corresponds to a zero calibration of the system and
is executed only if the weight is stable and below the set value.
Value from 0 to the value of the CAPAC parameter.
Default: 0