manualshive.com logo in svg
background image

Equalizing The Working Pressure of All Divider Block Outlets Ensures

Cylinders, Rings, Rods & Packing Are Receiving The Calculated Volume of Oil

NOTICE:

 The

 

EQUALIZER

 should be manually  adjusted to preset pressure before installation  on the 

divider block system. Locate any convenient section of tubing between the outlet of the divider block and the 
injection check valve, remove approx 3" of tubing and install the 

EQUALIZER

1)

 With the compressor operating at max RPM and discharge pressure,

 note the maximum pressure reading on the pressure 

gauge installed on the discharge of the lubricator pump or inlet of the divider block.

 (see fig 1)

2) 

Loosen lock nut with a 5/8" open end wrench and slowly rotate clockwise to increase pressure while monitoring the pressure 

 

gauge on the divider block or lube pump.  

Note:

 If needed a pressure gauge may be temporarily placed in the tubing line to simplify 

making minor adjustments to the opening pressure on the 

EQUALIZER

(see fig 3)

3)

 Slowly increase pressure by rotating the adjusting nut on the 

EQUALIZER

 clockwise until you notice the pressure increasing 

on the divider block system gauge. 

 

(see fig 4)

 

4)

 Continue monitoring the pressure gauge at the discharge of the lube pump (or inlet of the divider block) and slowly rotate the 

adjusting nut clockwise until the pressure gauge begins to read approximately 300 PSI over the initial system pressure.

5)

 After installing and adjusting the

 EQUALIZER

, the gauge should display pressure 300 PSI over the highest peak pressure of 

the system BEFORE the 

EQUALIZER

 was adjusted. To secure the pressure setting, use an open end 5/8" wrench as backup 

and tighten the lock nut against the adjusting nut. 

(see fig 3 & 4)

6)

 Continue installing and adjusting 

EQUALIZERS

 on all outlets of the divider block until the pressure gauge holds consistent 

pressure with no more than 200 PSI rise and fall. 

 As you install and adjust the other 

EQUALIZERS

, the goal is never to 

NOTE:

increase the pressure reading on the gauge at the pump or divider block after adjusting the first 

EQUALIZER

.

7)

 After adjusting all 

EQUALIZERS

, the indicator needle on the pressure gauge at the lubricator pump or divider block should 

fluctuate very little with fluid movement and no erratic pressure changes over 200 psi.

8)

 If the pressure gauge at the pump rises and falls erratically over 200 psi, re-adjust each 

EQUALIZER

 until the pressure gauge 

shows less than 200 PSI differential with fluid movement. 

NOTE:

 After you've set all 

EQUALIZERS

 to the desired opening pressure, spread Cross Check Torque Seal over the adjusting 

nut and lock nut 

. If the torque seal is broken it's obvious someone has tampered with the set pressure.

(see fig 2 & 3)

ADJUSTING NUT

on 

"EQUALIZER"

Rotate to Increase

or Decrease Pressure

PATTON

DIVIDER BLOCK SYSTEMS

  12 T

  15 T

  06 T

(fig 4)

 

LOCK NUT

(fig 3)

 

Pressure Gauge

Discharge Of Pump

or Inlet of Divider Block

(fig 1)

 

1st Stage Cyl.
@ 300 PSI

2nd Stage Cyl.
@ 800 PSI

2nd Stage Pkg.
@ 400 PSI

1st Stage Cyl.
@ 300 PSI

1st Stage Pkg.
@ 200 PSI

2nd Stage Cyl.
@ 800 PSI

500

0

1000

1500

2000

2500

3000

3500

4000

II

I II

I

I

I

I

I

I

I

I

II

II

I

I

I

I

I

I

I

I

II

I I I

L U B R I C A T O R     P R O D U C T S

PATTON

DIVIDER BLOCK SYSTEMS

(fig 2)

INLET

(fig 5)

OUTLET

 Minor Adjustment Of The 

"EQUALIZER"

After Installation In The Tubing Line of The Divider Block System

EQUALIZER

500

0

1000

1500

2000

2500

3000

3500

4000

II

I II

I

I

I

I

I

I

I

I

II

II

I

I

I

I

I

I

I

I

II

I I I

L U B R I C A T O R     P R O D U C T S

Отзывы: