Due to the variety of problems that can be caused by outside weather conditions, venting by canopies or wall 

fans  is  preferred  over  any  type  of  direct  venting.    It  is  recommended  that  a  canopy  extend  6"  past  the 

appliance and the bottom edge be located 6'6" from the floor.  Filters should be installed at an angle of 45° or 

more  from  the  horizontal.    This  position  prevents  dripping  of  grease  and  facilitates  collecting  the  run-off 

grease in a drip pan, unusually installed with a filter.  A strong exhaust fan tends to create a vacuum in the 

room  and  may  interfere  with  burner  performance  or  may  extinguish  pilot  flames.    Fresh  air  openings 

approximately equal to the fan area will relieve such a vacuum.  In case of unsatisfactory performance on 

any appliance, check the appliance with the exhaust fan in the “OFF” position.  Do this only long enough to 

check equipment performance, then turn hood back on and let it run to remove any exhaust that may have 

accumulated during the test. 
The exhaust fan should be installed at least 2 feet above the vent opening at the top of the fryer. 
Make sure all ventilation meet local code requirement 
This unit is not intended to be connected directly to an outside flue. 

Step 5: Gas connection 

A 3/4" male NPT line for the gas connection is located near the lower right rear corner of the fryer. The serial 

plate (located inside the front door of the fryer) indicates the type of gas the unit is equipped to burn (natural 

gas or propane). The fryer should be connected ONLY to the type of gas for which it is equipped. 
A circuit diagram is located inside the front door of the fryer. 
This  equipment  is  adjusted  at  the  factory;  however,  pilot  height  should  be  checked  at  installation  and 

adjusted, if necessary. 
For orifice sizes and pressure regulator settings, see the chart on page 4. If the fryer is being installed at over 

2,000 feet altitude and that information was not specified when ordered, contact the appropriate authorized 

Service Representative  or the Service Department. Failure to  install  with  proper orifice sizing  will result in 

poor performance and may void the warranty. 
If  applicable,  the  vent  line  from  the  gas  appliance  pressure  regulator  shall  be  installed  to  the  outdoors  in 

accordance  with  local  codes  or,  in  the  absence  of  local  codes,  with  the

  National  Fuel  Gas  Code,  ANSI 

Z223.1

Natural  Gas  Installation  Code,  CAN/CGA-B149.1

,  or  the

  Propane  Installation  Code,  CAN/CGA-

B149.2

, as applicable. 

An  adequate  gas  supply  is  imperative.  Undersized  or  low  pressure  lines  will  restrict  the  volume  of  gas 

necessary for satisfactory performance. A combination gas valve and pressure regulator, which is provided 

with each unit, is set to maintain a 4" W.C. manifold pressure for natural gas or 10.0" W.C. manifold pressure 

for propane gas. However, to maintain these conditions the pressure on the supply line, when all units are 

operating  simultaneously,  should  not  drop  below  7"  W.C.  for  natural  gas  or  11"  W.C.  for  propane  gas. 

Fluctuations of more than 25% on natural gas or 10% on propane gas will create problems and affect burner 

operating  characteristics.  A  1/8"  tap  to  measure  the  manifold  pressure  is  located  on  the  combination  gas 

valve, which is on the burner manifold located directly below the burners inside the cabinet. 
Purge the supply line to clean out dust, dirt, or other foreign matter before connecting the line to the unit.  
It is recommended that an individual manual shutoff valve be installed in the gas supply line to the unit.  
Use pipe joint compound that is suitable for use with both natural and LP gas on all threaded connections. 

Содержание PT-F3-LP

Страница 1: ...E INJURY OR DEATH READ THE INSTALLATION OPERATING AND MAINTENANCE INSTRUCTIONS THOROUGHLY BEFORE INSTALLING OR SERVICING THIS EQUIPMENT Please call the Service Department and ask for contact informati...

Страница 2: ...could result in injury product damage or property damage NOTICE This symbol refers to information that needs special attention or must be fully understood even though not dangerous WARNING FIRE HAZAR...

Страница 3: ...of reliable trouble free operation For best results read this manual carefully RETAIN THIS MANUAL FOR FUTURE REFERENCE MODELS This manual is for Gas floor model Fryers with 40 lbs 50 lbs and 90 lbs ca...

Страница 4: ...Height in Gas Connection in Total BTU hr Crated Weight lbs A B C D E F G H I 3 burner fryer 15 5 14 0 30 3 14 0 47 2 34 7 6 0 4 2 7 0 90 000 150 4 burner fryer 15 5 14 0 30 3 14 0 47 2 34 7 6 0 4 2 7...

Страница 5: ...50 000 39 Propane 10 W C 5 30 000 150 000 52 Minimum supply pressure is 4 W C for natural gas and 10 W C for propane Orifice sizes are for units installed at altitudes between 0 and 2000 feet above se...

Страница 6: ...are pre mounted on the base plates 1 Raise fryer sufficiently to allow legs or casters to be screwed into the base plate For safety shore up and support the fryer with an adequate blocking arrangemen...

Страница 7: ...iance is moved to its original installed position WARNING When this appliance is installed with casters it must be installed with the casters supplied a connector complying with either ANSI Z21 69 or...

Страница 8: ...8 Step 3 Flue Installation 1 Unpack the flue box and flue wrap 2 Slide the flue box over the flue and secure it with the two self tapping screws using a 5 16 socket 3 Slide the flue wrap over the flue...

Страница 9: ...FLOOR MODEL FRYERS SHALL BE INSTALLED WITH AT LEAST A 16 INCH SPACE BETWEEN THE FRYER AND SURFACE FLAMES FROM ADJACENT EQUIPMENT A FLAME GUARD IS ACCEPTABLE IF ALLOWED UNDER LOCAL CODE No additional s...

Страница 10: ...cked at installation and adjusted if necessary For orifice sizes and pressure regulator settings see the chart on page 4 If the fryer is being installed at over 2 000 feet altitude and that informatio...

Страница 11: ...SURES IN EXCESS OF 14 WC 1 2 PSIG or 3 45 kPa If the incoming gas pressure is in excess of 14 WC 1 2PSI 3 45 kPa a proper step down regulator will be required See PHOTO 1 for LP application Connect th...

Страница 12: ...knob down use a lit match to ignite the pilot Continue to press the knob down for about 30 seconds If the pilot does not stay lit when the knob is released repeat the lighting procedure and keep the k...

Страница 13: ...BURNERS WHEN THE FRYPOT IS EMPTY 7 To prevent burning or scorching the solid shortening keep the thermostat set at the lowest temperature until all the solid shortening between and above the tubes has...

Страница 14: ...d food CLEANING The equipment is constructed with the best quality materials and is designed to provide durable service when properly maintained To expect the best performance your equipment must be m...

Страница 15: ...residue from stainless steel use ordinary soap and water with or without detergent applied with a sponge or cloth Dry thoroughly with a clean cloth Never use vinegar or any corrosive cleaner To remove...

Страница 16: ...ontact your Service Representative for reliable service dependable advice or other assistance and for genuine factory parts All units are adjusted at the factory In case of problems in operation at in...

Страница 17: ...ace adjustment screw cap CHECKING AND ADJUSTING CALIBRATION OF THERMOSTAT All thermostat controls are carefully calibrated at the factory i e the dial is properly set to control appliance temperatures...

Страница 18: ...ed Combination gas valve is in OFF position Pilot gas not adjusted properly Gas supply to unit off Bad thermopile Dirty thermopile connections at combination gas valve or high limit Clogged orifice Dr...

Страница 19: ...19 Wiring Diagram...

Страница 20: ...cement parts may be ordered either through a Authorized Parts Distributor or a Authorized Service Agency When ordering parts please supply the Model Number Serial Number Part Number and Description In...

Страница 21: ...sys 4 PT 400146 1 Combination valve LP _Invensys 4 PT 400242 1 Combination Valve Nat _Honeywell 4 PT 400246 1 Combination valve LP _Honeywell 5 PT 400070 1 Tubing fryer pilot 10 PT 300031 ea Burner Fr...

Страница 22: ...T 400076 1 Flue top removable 4 tube fryer PT 400077 1 Flue top removable 5 tube fryer 6 PT 400078 1 Flue wrap top removable 3 and 4 tube fryer PT 400079 1 Flue wrap top removable 5 tube fryer not sho...

Страница 23: ...We all recognize however that replacement parts and occasional professional service may be necessary to extend the useful life of this unit When service is needed contact an Authorized Service Agency...

Страница 24: ...ntiguous United States Hawaii and metropolitan areas of Alaska and Canada may vary The following conditions are not covered by warranty Equipment failure relating to improper installation improper uti...

Отзывы: