32
PAL2
PAL1
ASEt
ALARM SET FLOW CHART
TABLE 3-3 ALARM SET MODE CONFIGURATION PROCEDURE
Press and release the SCROLL key until ASEt is displayed, then press the DOWN key. Press
the SCROLL key to advance the display through the parameters and their values. Use the UP
and DOWN keys to select (adjust) the values. After selecting a parameter, press the SCROLL
key to proceed to the next parameter. Pen 1 selections will appear in the Pen 1 window and
the Pen 2 ( if provided) selections will appear in the Pen 2 window. After all selections have
been made, press the UP key with a parameter in the display (not a setting) to exit the mode.
DISPLAY AVAILABLE
FACTORY YOUR
STEP
DESCRIPTION CODE SETTINGS
SETTING SETTING
1
Process Alarm 1
PAL1
-9999 to 9999 degrees/units
0
2
Process Alarm 2
PAL2
-9999 to 9999 degrees/units
0
If ASEt does not appear on the display refer to the Enable mode section of this manual for
directions on how to determine if the ASEt mode is enabled. If ASEt appears on the display,
but pressing the DOWN key causes the display to change to oFF, this indicates that no
alarm(s) have been selected in the Program mode.
ALARM OPERATION
There are two types available per pen, Process Direct or Process Reverse. These are
selected in the Program mode.
Process Alarm Direct - the alarm will be ON if the process value is greater than the process
alarm value selected in the Alarm Set mode.
Process Alarm Reverse - the alarm will be ON if the process value is less than the process
alarm value selected in the Alarm Set mode.
The alarms will be active while the instrument is in the Operate mode.
Alarm output chatter can be reduced by using the hysteresis (adjusted in Program mode) to
create a deadband around the alarm point.
LIMIT SETPOINT OPERATION
The instrument must be in the Operate mode to allow setpoint value to be displayed and
adjusted. In the Operate mode, to view the setpoint, press and release the UP or DOWN key.
The displayed value is the setpoint. To change the setpoint value, press and hold the
appropriate key. Press and hold the UP key to increase the setpoint or press and hold the
DOWN key to decrease the setpoint. The setpoint will change slowly at first then faster as the
key is held.
To reset the limit output, press the RESET key after the limit condition has been cleared.
NOTE: The setpoint cannot be changed if the Limit setpoint has been exceeded.
ON
OFF
Actual Display
On/Off Display -
Use arrow keys
to turn on or off
Scroll Key
Numeric Display -
Use arrow keys
to change value
Up Arrow Key
Down Arrow
KEY
Содержание MRC 7000
Страница 27: ...27 CbS CAd1 CAd2 CCon D Com Optional Coo...
Страница 61: ...61...
Страница 62: ...62...
Страница 63: ...63...
Страница 64: ...64...