MIC 1400 Manual
Edition 1
48
Engineering Units Upper
This parameter, applicable only if a linear input is specified, defines the
scaled input value when the process variable input is at its maximum value.
It is adjustable between -1999 to 9999. The default value is 1000. This
parameter can be set to a value less than (but not equal to) Engineering
Units Lower, in which case the sense of the input is reversed. Display code
is Euu.
Engineering Units Lower
This parameter, applicable only if a linear input is specified, defines the
scaled input value when the process variable input is at its minimum value.
It is adjustable between -1999 and 9999. The default value is 0. This pa-
rameter can be set to a value greater than (but not equal to) Engineering
Units Upper, in which case the sense of the input is reversed. Display code
is EuL.
Pre-Tune Enable/Disable
This parameter determines whether or not the instrument Pre-Tune mode is
activated on power up or not (0=disabled, 1=enabled). Default is 0. Dis-
play code is EPtn.
Manual Mode Enable/Disable
This parameter determines whether operator selection of manual control is
enabled or disabled (0=disabled, 1=enabled). The default setting is 0.
Display code is ESby.
Setpoint Ramp Enable/Disable
This parameter enables/disables use of the Setpoint Ramp feature (0=dis-
abled, 1=enabled). The default setting is 0. Display code is ESPr.
Communications Enable
This parameter enables/disables the changing of parameter values via the
RS485 communications link, if the Communications option is specified.
Settings are 0=disabled and 1=enabled. Default setting is 0. Display code
is CCon.