background image

EN

 | Operating manual 

Maintenance and repair of the dryer

  WVM 40 -1450 

 

43

  Depressurise dryer and take out of service 

(see page 37).

  Remove the base of the fi lter housing.

  Remove fi lter element by turning it.

  Renew fi lter element.

  Mount the base of the fi lter housing.

  Dispose of spent fi lter element according to 

the statutory regulations.

  If no other maintenance work is required: 

Restart dryer (see page 38). Check fi lter for 

leaks.

Open control air fi lter

Renew dewpoint sensor 

In order to ensure accurate dew¬point measuring, we recommend annually renew the dew-

point sensor at least every 12 months. The recalibration must be carried out by the manu-

facturer. This period depends however on the actual application and might thus be extended 

accordingly.

Warning!

The dew point sensor is a sensitive measuring device. It can be damaged if 

subjected to forceful vibrations or shocks. Therefore, please handle the dew 

point sensor with great care at all times.

In order to limit the impact on the dryer operation to a minimum, we recommend that you 

contact the manufacturer well in advance (for contact details, see page 6) and order a new 

dewpoint sensor. 

After receipt of the new pressure dewpoint sensor, replace the sensor as follows:

  Hold the box of the dewpoint sensor ready.

  Release pressure from dryer and shut down the unit (see page 36).

  Loosen the screw at the adapter (1) and disconnect signal cable with the adapter and 

seal. 

  Remove dewpoint sensor from the sensor cell (3) by turning the nut (2).

  Take the new dewpoint sensor (2) from the box, remove the protective caps (4, 5) and 

Содержание Zander WVM 40

Страница 1: ...WVM 40 1450 Adsorption dryer Operating manual Revision 04 06_2018 EN Cod 398H271785...

Страница 2: ......

Страница 3: ...es 28 Connection of electrical components 29 Start up 30 Requirements for initial commissioning 30 Overview of the operating and display elements 30 Commissioning of the dryer 31 Preparation for commi...

Страница 4: ...EN Operating manual 4 WVM 40 1450 Notes on error messages and errors 48 Appendix Technical Documents 49 Technical data overview of standard dryers 50 Spare parts list 52...

Страница 5: ...is obliged to enter missing unit data in the above table regularly update the unit data The above device specifications are necessary to quickly identify the dryer and its compo nents and facilitate...

Страница 6: ...ementary documents Supplementary documents such as operating manuals for options or pertaining components must always be heeded They contain additional information e g regarding maintenance and are th...

Страница 7: ...box Note These notes provide you with hints and information on the safe and ef cient handling of machines and devices Warning These safety notes warn against damage to property and help you to avoid...

Страница 8: ...operated by non qualified personnel not used within its intended design specifications is repaired or maintained incorrectly Note For your own safety and to prevent machine damage please note the inf...

Страница 9: ...ly released through expansion and relief valves can lead to serious injury Hot surfaces During operation certain surfaces of the dryer reach temperatures above 120 C At insulated dryers screw connecti...

Страница 10: ...a climbing aid Pipes valves and similar fittings have not been designed for such loads They could fracture tear off or become damaged in another way General safety notes For your own safety when carr...

Страница 11: ...t sudden air ejection During expansion the pressure is released suddenly through the muf er A loud cracking noise occurs which can injure your hearing Particles carried in the air can injure your eyes...

Страница 12: ...ng compressed air Never leave tools loose parts or cloths in at or on the dryer Following maintenance work always check all flange and bolt connections for leakage and secure seating Only use replacem...

Страница 13: ...outlet valve l 7 Pressure transducer 2 Control air filter and pressure reducer 8 Vessel 3 Filler sleeve for desiccant 9 Dew point measuring chamber 4 Switch cabinet with operating panel 10 Pressure bu...

Страница 14: ...se button for the safety thermostat 1 Resistance thermometer for regeneration gas final temperature 6 Suction opening for regeneration gas 2 Vacuum pump 7 Heater 3 Lashing eye 8 Expansion valve with s...

Страница 15: ...wo vessels alternate between different operating modes Whilst in one ves sel compressed air is de humidified adsorption in the other vessel the humid drying agent is prepared for another charge regene...

Страница 16: ...er as a low hum Expansion phase Heating phase duration several hours A vacuum pump sucks ambient air through the heater to the vessel to be regenerated The air is thereby heated by the heater The warm...

Страница 17: ...via the pressure build up line The vessel can now be switched from regeneration to absorption operation Pressure build up Stand by phase for dewpoint measurement option The regenerated vessel remains...

Страница 18: ...The heater Adaptation for outdoor installation The standard dryer is designed for installation in confined places and not for outdoor opera tion because the following factors affect its function and...

Страница 19: ...m heat exchanger comes with an appropriate steam shut off valve In this case the scope of delivery can also comprise supplementary documents such as data sheets or supplementary operating manuals Stea...

Страница 20: ...es Use these eyes to secure the unit during transport Only use suitable and technically perfect lifting gear with a sufficient carrying capacity During transportation the dryer must be carefully secur...

Страница 21: ...generation and a suitable pressure dew point A higher ambient temperature or relative humidity must be specially considered when designing the dryer and recorded in the offer document if this proves t...

Страница 22: ...s The dryer should be erected with sufficient clearance above to the sides and behind so that maintenance work can be carried out and the drying agent can be changed without hindrance see illustration...

Страница 23: ...t the vessel top to lift the dryer Remove packaging Attach suitable lifting gear to the lifting eyes on the vessels see Item 1 on the adjacent illustration The lashing eyes Item 2 are intended to secu...

Страница 24: ...se cover dryer with a tarpaulin The ambient temperature in the storage room may not be below 1 C To storage the dryer proceed as follows Decommission dryer as described on page 36 Ensure that the inle...

Страница 25: ...nd storage WVM 40 1450 25 Note To recommission the dryer after prolonged storage please proceed as descri bed for initial commissioning see page 31 Store drying agents Do not store drying agents in th...

Страница 26: ...requirements described here are not met This can also degrade the dryer s function For proper installation the operator must provide the following Connections and lines must be provided for compresse...

Страница 27: ...o pre vent foreign objects or animals from entering the dryer The outlet line must be installed in such a way that there is no risk of injury from hot regeneration gas Rainguard when lines point upwar...

Страница 28: ...o the compressed air system while heeding rated diameter and pressure The figure below shows a proper installation Compressed air system Item Component 1 Dryer 2 Humid air inlet 3 Compressed air inlet...

Страница 29: ...e terminal strip the circuit diagram is attached inside the switch cabinet Connect the dryer s earth cable to the PE terminal Protect the dryer against short circuits by installing fuses to all phases...

Страница 30: ...ed air can flow through the dryer Operators for the components are available Inspection to be carried out prior to commissioning all pipe cable and screw connections have been retightened none of the...

Страница 31: ...ted to temperatures of over 120 C At insulated dryers screw connections might protrude from the insulation Do not touch hot surfaces Allow surfaces to cool before you carry out any work at the dryer R...

Страница 32: ...pressure increase at the vessel pressure gauge see page 13 In one of the vessels the pressure must be increased until it reaches the operating pressure Compressed air inlet to the dryer Avoid abrupt...

Страница 33: ...olour of the housing and extends over several cooling fins Wait until the vacuum pump is fully started Then stop the dryer The fan wheel continues rotating for a short period of time During this time...

Страница 34: ...ee above Commissioning of dryer Set main switch to position I Start dryer see the operating manual for the controller The unit is now fully switched on provided that no error message is displaye How t...

Страница 35: ...This is the case if the operating parameters match or slightly fall below the specified values Dryer performance can degrade if the dryer often operates at part load Dryer performance increases as soo...

Страница 36: ...ve The dryer is now shut down Restart the dryer only after having eliminated all errors Stopping the dryer Please proceed as follows if no compressed air is needed at night or at weekends When the com...

Страница 37: ...regenerated at the same time Depressurise the adsorbing vessel e g by opening the manual drain valve on the downstream filter Wait until the pressure on the vessel pressure gauge of the adsorbing vess...

Страница 38: ...manual for the controller If necessary slowly open the compressed air inlet and outlet valves installed by the operator The dryer is now ready for operation and continuous automatic cycle If compress...

Страница 39: ...maintenance work only when the plant has been shut down and depressur ised Bolt connections must be undone with care Note ram pressure values Otherwise emerging media may cause personal injury Do not...

Страница 40: ...ew 42 Vacuum pump Inspect bearing and replace if necessary 44 Dust filter Check dust filter for contamination and clean if necessary 44 Desiccant Check desiccant for contamination and replace if neces...

Страница 41: ...the dryer and shut it down see page Depressurising and shutting down the dryer 37 Dam pressure can be caused by a blocked muffler a malfunction of the expansion valve a leaking pressure build up valve...

Страница 42: ...njure persons and damage property Silencer elements should therefore be checked annually and replaced if soiled Beware of sudden air blast Pressure suddenly escapes via the silencer during expansion A...

Страница 43: ...n the actual application and might thus be extended accordingly Warning The dew point sensor is a sensitive measuring device It can be damaged if subjected to forceful vibrations or shocks Therefore p...

Страница 44: ...idges and the vessels We therefore recommend that you carry out these tasks together Note In accordance with national regulations a pressure vessel inspection may be prescribed to be carried out at re...

Страница 45: ...years Under favourable conditions the desiccant might not have to be replaced at that stage and can be used for longer period see also page 21 However the service life depends greatly on the contamin...

Страница 46: ...t be contami nated with pollutants Please take this into account when disposing of the desiccant Notes on the disposal of used desiccant As the used desiccant is contaminated with various substances i...

Страница 47: ...make sure to heed the next step Use a funnel if neces sary Unscrew the sleeve plug Make sure to compact the filling in the vessel Equip the sleeve plug with a non locking thread seal and screw in Repe...

Страница 48: ...mostat V Vacuum pump Notes on error messages and errors The error message from the dryer are displayed on the operating panel The controller manual provides appropriate information You are given infor...

Страница 49: ...nical Documents The appendix of this operating manual contains the following technical documents and data Technical data List of service and desiccant kits Process diagram Pneumatic diagram of the con...

Страница 50: ...400 300 25 WVM 150 1500 1350 18 20 1300 470 375 25 WVM 200 1980 1782 23 70 1650 656 550 25 WVM 235 2350 2115 36 70 2000 827 750 25 WVM 300 2930 2637 36 70 2250 910 750 25 WVM 355 3550 3195 43 70 2650...

Страница 51: ...g to other Typ WVM 40 WVM 1450 Fluid class according to PED 2 Supply voltage see type plate Protection class IP54 min max Operating overpressure bar see type plate Ambient temperature C 1 50 Max intak...

Страница 52: ...es wear parts kit for the expansion valve V5 wear parts kit for the pressure build up valve V4 SKW410 W710 VM4 24 WVM 410 710 24 month SKW800 W1080 VM4 24 WVM 800 1080 24 month SKW1230 W1450 VM4 24 WV...

Страница 53: ...50DESMIX WVM 475 WVM475DESMIX WVM 65 WVM65DESMIX WVM 525 WVM525DESMIX WVM 85 WVM85DESMIX WVM 620 WVM620DESMIX WVM 120 WVM120DESMIX WVM 710 WVM710DESMIX WVM 150 WVM150DESMIX WVM 800 WVM800DESMIX WVM 20...

Страница 54: ...00W 1 Flat gasketsDN200 WVM 1230 1450 GASKIT250W 1 Flat gasketsDN250 WVM 40 355 SDD 25 AL 1 Silencers WVM 410 1080 SDD 25 AL 2 Silencers WVM 1230 1450 SDD 40 AL 6 Silencers WVM 40 1450 ZHM100 450 1 de...

Страница 55: ......

Страница 56: ...co MI Italy Sede Operativa Gas Separation and Filtration Division EMEA Strada Zona Industriale 4 35020 S Angelo di Piove PD Italy tel 39 049 971 2111 fax 39 049 9701911 Web site www parker com hzd e m...

Отзывы: